Use 3082A when the page's ODVA line is Class 2 Thick. Use 3084A when that line is Class 2 Thin.

Rust Belt Industrials · October 24, 2026 · 6 min read

On this page

Use Belden 3082A when the cable is ODVA Class 2 Thick. As of October 24, 2026, that page lists one 15 AWG power pair, one 18 AWG data pair, a nominal jacket diameter of 0.480 in (12.2 mm), and 16 A per power conductor at 30°C. Use Belden 3084A when the cable is ODVA Class 2 Thin. As of the same day, that page lists one 22 AWG power pair, one 24 AWG data pair, a nominal jacket diameter of 0.280 in (7.11 mm), and 6 A per power conductor at 30°C. Both data pairs list 120 Ohm. PROFIBUS DP at 150 Ohm is Belden 3079A, on the DP and PA page.

Thick and Thin are two Belden constructions

As of October 24, 2026, Belden 3082A is titled DeviceBus, 2 pair, 15+18 AWG stranded tinned copper, with PVC and foam polyethylene insulation, individual Beldfoil and an overall tinned-copper braid at 65%, and a PVC jacket listed CMG PLTC-ER. The power pair is 15 AWG, 19x27, tinned copper. The data pair is 18 AWG, 19x30, tinned copper. Power insulation is PVC, red and black, 0.021 in (0.53 mm) thick, with a nominal insulation diameter of 0.109 in (2.77 mm). Data insulation is foam polyethylene, blue and white, 0.053 in (1.3 mm) thick, with a nominal insulation diameter of 0.150 in (3.81 mm), and the notes cell says HDPE. Each pair has a 100% bi-laminate tape. The outer braid is 65% tinned copper with an 18 AWG (19x30) tinned-copper drain. The jacket is PVC, 0.060 in (1.5 mm), nominal diameter 0.480 in (12.2 mm), with a jacket OD tolerance of 0.010 in.

As of October 24, 2026, Belden 3084A is titled DeviceBus, 2 pair, 22+24 AWG stranded tinned copper, with the same insulation and shield pattern and a PVC jacket listed CMG, CL2. The power pair is 22 AWG, 19x34, tinned copper. The data pair is 24 AWG, 19x36, tinned copper. Power insulation is PVC, red and black, 0.021 in (0.53 mm), nominal insulation diameter 0.072 in (1.8 mm). Data insulation is foam polyethylene, blue and white, 0.026 in (0.66 mm), nominal insulation diameter 0.077 in (2.0 mm). Each pair has a 100% bi-laminate tape. The outer braid is 65% tinned copper with a 22 AWG (19x34) tinned-copper drain. The jacket is PVC, 0.032 in (0.81 mm), nominal diameter 0.280 in (7.11 mm), with a jacket OD tolerance of 0.005 in.

Decision rows from the Belden 3082A and 3084A pages opened October 24, 2026.
Item3082A3084A
ODVA lineClass 2 ThickClass 2 Thin
Power pair15 AWG, 19x27, tinned copper22 AWG, 19x34, tinned copper
Data pair18 AWG, 19x30, tinned copper24 AWG, 19x36, tinned copper
Nominal jacket OD0.480 in (12.2 mm)0.280 in (7.11 mm)
Power current16 A per conductor at 30°C6 A per conductor at 30°C
Data current14 A per conductor at 30°C4 A per conductor at 30°C
Data impedance120 Ohm120 Ohm
UL voltage rating300 V (CMG, PLTC-ER), 600 V (AWM 20201)300 V (CMG, CL2), 600 V (AWM 20201)

Current and impedance stay on the pair that prints them

As of October 24, 2026, the 120 Ohm cell, the 12 pF/ft (39 pF/m) capacitance, the 1.36 ns/ft delay, and the 75% velocity are on the data pair of both 3082A and 3084A. The power-pair impedance cell on both pages is empty, so the request copies 120 Ohm onto the data pair. Power-pair inductance on 3082A is 0.174 µH/ft (0.571 µH/m). On 3084A, power-pair inductance is 0.221 µH/ft (0.725 µH/m) and data-pair inductance is 0.251 µH/ft (0.823 µH/m). Nominal conductor DCR on 3082A is 3.58 Ohm/1000ft for the power pair and 7.2 Ohm/1000ft (24 Ohm/km) for the data pair. Nominal conductor DCR on 3084A is 18.2 Ohm/1000ft for the power pair and 28.8 Ohm/1000ft (94.5 Ohm/km) for the data pair. Outer-shield DCR is 7.29 Ohm/1000ft (23.9 Ohm/km) on 3082A and 5 Ohm/1000ft (16 Ohm/km) on 3084A.

The max-conductor-DCR cells on the 3084A page opened October 24, 2026 were left off this guide. The power max, 17.5 Ohm/1000ft, sits below the nominal 18.2 Ohm/1000ft, and the data max is printed as 28 Ohm/100m beside a nominal in Ohm/1000ft. Copy the nominal conductor DCR. Inner-shield DCR cells were also left off, so a shield resistance on the request comes from a later reading of that column.

Voltage, temperature, and bend are printed per cable

As of October 24, 2026, both pages list a second voltage cell of 300 V (AWM I/II A), a UL temperature of 60°C, and an operating range of -20°C to +60°C. The listings that differ are the first UL voltage cell and the tray listing: 3082A is 300 V (CMG, PLTC-ER) and 600 V (AWM 20201), with NEC Article 725, Article 800, CMG, and PLTC. 3084A is 300 V (CMG, CL2) and 600 V (AWM 20201), with NEC Article 725, Article 800, CL2, and CMG. Both name AWM 20201 and AWM I/II A, and both name C(UL) CMG. Minimum bend radius, stationary and installation, is 5.76 in (146 mm) on 3082A and 2.8 in (71 mm) on 3084A. Maximum pull tension is 192.6 lbs (87.36 kg) on 3082A and 70.06 lbs (31.78 kg) on 3084A. Bulk weight is 128 lbs/1000ft on 3082A and 44 lbs/1000ft on 3084A.

Environmental suitability on both pages opened October 24, 2026 is indoor, outdoor, sunlight resistance, and oil resistance. Flammability on 3082A is UL 1685 FT4 Loading, IEEE 1202 FT4, and IEC 60332-1-2, with CPR Euroclass Eca. Flammability on 3084A is UL 1685 UL Loading, IEEE 1202 FT4, and IEC 60332-1-2, with CPR Euroclass Eca and CPR UKCA Class Eca. The 3084A notes add a flex life of plus or minus 90 degrees, 2 in diameter, 2 lbs tension, 2000 cycles minimum. Both notes say the jacket carries meter marks. The 3082A notes say the jacket is printed 1PR16 instead of 1PR15 because of the UL CMG listing, and the notes line begins with the word Thick. The 3084A notes do not use the word Thin. The Class 2 Thin line is the other-standard cell. Page revision is 0.607, dated 02-20-2026, on 3082A, and 0.611, dated 02-20-2026, on 3084A.

What to copy onto the cable line

  • Part: 3082A or 3084A, from the page opened October 24, 2026.
  • ODVA line: Class 2 Thick on 3082A, or Class 2 Thin on 3084A.
  • Power pair and data pair gauges, and the nominal jacket diameter.
  • Power current and data current at 30°C.
  • 120 Ohm on the data pair. Leave the power-pair impedance blank.
  • The UL voltage cell for that part: PLTC-ER on 3082A, or CL2 on 3084A.

DeviceNet cable note

Name 3082A or 3084A and the ODVA class line on that page.

This prepares a request. It does not send one.

Questions the two Belden pages answer

Does 120 Ohm pick Thick or Thin?

Both data pairs list 120 Ohm, as of October 24, 2026. The ODVA line, the gauges, and the jacket diameter pick the cable. A request that says only 120 Ohm has not chosen 3082A or 3084A.

Which current is the power pair?

On the page opened October 24, 2026, 3082A lists 16 A per power conductor at 30°C and 14 A per data conductor at 30°C. 3084A lists 6 A per power conductor and 4 A per data conductor, both at 30°C.

Can the PLTC-ER line be copied onto 3084A?

PLTC-ER is on the 3082A voltage and compliance lines. 3084A's matching lines say CL2 and CMG. Each cable keeps the listing printed on its own page as of October 24, 2026.

Sources

Gauges, diameters, currents, impedance, voltage, temperature, bend, weight, ODVA class lines, and the jacket notes are from the Belden 3082A and 3084A product pages. Both were opened October 24, 2026. Max conductor DCR on 3084A, and inner-shield DCR on both pages, were left off the comparison.