Belden 3084A PVC or 3085A CPE for DeviceNet Thin

Use 3084A for Thin PVC at 60°C with 4 A on the data pair. Use 3085A for Thin CPE at 75°C with 6 A on the data pair. Both are 0.280 in, and both power pairs are 6 A.

Rust Belt Industrials · October 29, 2026 · 6 min read

On this page

Use Belden 3084A when the ODVA Class 2 Thin cable is the PVC jacket. As of October 29, 2026, that sheet lists a nominal jacket diameter of 0.280 in (7.11 mm), 4 A per data conductor at 30°C, UL temperature 60°C, and operating temperature -20°C to +60°C. Use Belden 3085A when the Thin cable is the CPE jacket. As of the same day, that sheet lists the same 0.280 in (7.11 mm) diameter, 6 A per data conductor at 30°C, UL temperature 75°C, and operating temperature -20°C to +75°C. Both power pairs list 6 A per conductor at 30°C. Both data pairs list 120 Ohm. Thick PVC against Thick CPE is on the 3082A and 3083A page.

Both sheets say Class 2 Thin, at the same 0.280 in diameter

As of October 29, 2026, the other-standard cell on 3084A and on 3085A says ODVA Class 2 Thin. Both descriptions say DeviceBus for ODVA DeviceNet, two pair, 22 plus 24 AWG stranded tinned copper, PVC and foam polyethylene insulation, individual Beldfoil, and an overall tinned-copper braid at 65%. 3084A's jacket in the description is PVC, CMG, CL2. 3085A's jacket in the description is CPE, CMG, CL2. The power pair on both is 22 AWG, 19x34, tinned copper, PVC insulation, red and black, 0.021 in (0.53 mm), nominal insulation diameter 0.072 in (1.8 mm). The data pair on both is 24 AWG, 19x36, tinned copper, foam polyethylene, blue and white, 0.026 in (0.66 mm), nominal insulation diameter 0.077 in (2.0 mm). Each pair has a 100% bi-laminate tape. The braid is 65% tinned copper with a 22 AWG (19x34) tinned-copper drain. 3084A's jacket is PVC, 0.032 in (0.81 mm) thick. 3085A's jacket is CPE, 0.033 in (0.84 mm) thick. Both nominal diameters are 0.280 in (7.11 mm), and both jacket OD tolerances are plus or minus 0.005 in.

3084A and 3085A rows from the technical data sheets opened October 29, 2026.
Item3084A3085A
ODVA lineClass 2 ThinClass 2 Thin
JacketPVC, 0.280 inCPE, 0.280 in
Power current6 A at 30°C6 A at 30°C
Data current4 A at 30°C6 A at 30°C
Data impedance120 Ohm120 Ohm
UL temperature60°C75°C
Operating range-20°C to +60°C-20°C to +75°C
AWMAWM 20201 and AWM I/II ANo AWM line

Copy the nominal DCR, and keep the data current on its own sheet

As of October 29, 2026, both sheets list nominal power-conductor DCR of 18.2 Ohm/1000ft, nominal data-conductor DCR of 28.8 Ohm/1000ft (94.5 Ohm/km), inner-shield DCR of 7.95 Ohm/1000ft (26.1 Ohm/km) on the power pair and 7.45 Ohm/1000ft (24.4 Ohm/km) on the data pair, and outer-shield DCR of 5 Ohm/1000ft (16 Ohm/km). Data-pair impedance is 120 Ohm. Data-pair delay is 1.36 ns/ft. Data-pair velocity is 75%. 3084A's data capacitance is 12 pF/ft (39 pF/m). 3085A's data capacitance is 12.0 pF/ft (39.4 pF/m). Power-pair inductance on 3084A is 0.221 µH/ft (0.725 µH/m), and data-pair inductance is 0.251 µH/ft (0.823 µH/m). 3085A does not print an inductance cell. Power current is 6 A per conductor at 30°C on both. Data current is 4 A per conductor at 30°C on 3084A and 6 A per conductor at 30°C on 3085A.

The max-conductor-DCR cells were left off this page. On the sheets opened October 29, 2026, the power max of 17.5 Ohm/1000ft sits below the nominal 18.2 Ohm/1000ft, and the data max is printed as 28 Ohm/100m beside a nominal in Ohm/1000ft. That pair of cells is on 3084A and on 3085A. Copy the nominal conductor DCR. The Thick and Thin page already left the 3084A max cells off for the same reason.

60°C and AWM on the PVC sheet, 75°C and no AWM line on the CPE sheet

As of October 29, 2026, 3084A's UL voltage cell is 300 V (CMG, CL2) and 600 V (AWM 20201), plus a second voltage cell of 300 V (AWM I/II A). AWM compliance names AWM 20201 and AWM I/II A. NEC / UL compliance is Article 725, Article 800, CL2, CMG. UL temperature is 60°C. Operating temperature is -20°C to +60°C. Suitability is indoor, outdoor, sunlight resistance, and oil resistance. Flammability is UL 1685 UL Loading, IEEE 1202 FT4, and IEC 60332-1-2. CPR is Euroclass Eca and UKCA Class Eca. The notes give a flex life of plus or minus 90 degrees, 2 in diameter, 2 lbs tension, 2000 cycles minimum. 3085A's UL voltage cell is 300 V (CMG, CL2). It does not print a 600 V line or an AWM line. NEC / UL compliance is Article 725, Article 800, CL2, CMG. UL temperature is 75°C. Operating temperature is -20°C to +75°C. Suitability is indoor, outdoor, and sunlight resistance. The sheet does not print oil resistance. Flammability is UL 1685 FT4 Loading, IEEE 1202 FT4, and IEC 60332-1-2. CPR is Euroclass Eca. The notes say Thin and meter marks. They do not print the 2000-cycle flex line.

Bend radius, stationary and installation, is 2.8 in (71 mm) on both sheets, as of October 29, 2026. Maximum pull tension is 70.06 lbs (31.78 kg) on both. Bulk weight is 44 lbs/1000ft on 3084A and 46 lbs/1000ft on 3085A. Page revision is 0.611 on 3084A and 0.556 on 3085A, both dated 02-20-2026. 3085A's variant rows are bright yellow reels at 1,000 ft, 2,000 ft, and 5,000 ft.

What to copy onto the cable line

  • Part: 3084A or 3085A, from the sheet opened October 29, 2026.
  • ODVA line: Class 2 Thin on both.
  • Jacket: PVC or CPE, both at 0.280 in, tolerance 0.005 in.
  • Power current: 6 A at 30°C on both. Data current: 4 A at 30°C, or 6 A at 30°C.
  • Data impedance: 120 Ohm. Conductor DCR: the nominal cells, not the max cells.
  • Temperature: 60°C and -20°C to +60°C, or 75°C and -20°C to +75°C.
  • Listing: AWM 20201 on 3084A. 3085A's voltage cell is 300 V (CMG, CL2) and does not print AWM.
  • Flex: the 2000-cycle note is on 3084A. 3085A's notes do not print it.

3084A or 3085A note

Name the Thin part and copy the jacket, data current, and temperature from that sheet.

This prepares a request. It does not send one.

Questions these sheets answer

Does the CPE sheet keep 4 A on the data pair?

3084A lists 4 A per data conductor at 30°C, as of October 29, 2026. 3085A lists 6 A per data conductor at 30°C. The power-pair current stays 6 A on both.

Does CPE change the 0.280 in cell?

Both nominal jacket diameters are 0.280 in (7.11 mm), as of October 29, 2026. The jacket material is PVC on 3084A and CPE on 3085A. The thickness cells are 0.032 in and 0.033 in.

Which DCR cell is the one to copy?

Copy the nominal conductor DCR, 18.2 Ohm/1000ft on the power pair and 28.8 Ohm/1000ft (94.5 Ohm/km) on the data pair, as of October 29, 2026. The max cells disagree with those nominals and stay off the request.

Sources

Class, jacket, current, impedance, temperature, listing, and the flex note are from the Belden 3084A and 3085A technical data sheets. Both were opened October 29, 2026. The max-conductor DCR cells were read and left off the comparison.