Belden 9841 at 120 Ohm or 3079A at 150 Ohm

Use 9841 when the page titles the cable RS-485 at 120 Ohm. Use 3079A when the page titles it PROFIBUS DP at 150 Ohm.

Rust Belt Industrials · October 24, 2026 · Updated October 26, 2026 · 6 min read

On this page

Use Belden 9841 when the cable is the RS-485 construction at 120 Ohm. As of October 24, 2026, that page lists one 24 AWG (7x32) tinned-copper pair, a nominal jacket diameter of 0.232 in (5.89 mm), and 2.1 A per conductor at 25°C for a 10°C rise. Use Belden 3079A when the cable is the PROFIBUS DP construction at 150 Ohm. As of the same day, that page lists one 22 AWG solid bare-copper pair, a nominal jacket diameter of 0.315 in (8.00 mm), and 2.3 A per conductor at 25°C. A PA cable is a separate match, on the DP and PA page.

One pair on each page, with different gauge and color

As of October 24, 2026, the 9841 title is RS485, 1 pair 24 AWG stranded tinned copper, polyethylene insulation, overall Beldfoil and a 90% tinned-copper braid, PVC jacket, CM. Insulation thickness is 0.023 in (0.58 mm) and insulation diameter is 0.068 in (1.7 mm). Colors are white/blue stripe and blue/white stripe. The shield is a 100% bi-laminate tape with a 24 AWG (7x32) tinned-copper drain, plus a 90% tinned-copper braid. The jacket is PVC, 0.035 in (0.89 mm), nominal diameter 0.232 in (5.89 mm), with a jacket OD tolerance of 0.020 in.

As of October 24, 2026, the 3079A title is Profibus, 1 pair 22 AWG solid bare copper, polyethylene insulation, overall Beldfoil and a 65% tinned-copper braid, PVC jacket, PLTC CMG, PROFIBUS DP. Insulation is foam polyethylene, red and green, 0.035 in (0.89 mm) thick, insulation diameter 0.099 in (2.5 mm), and the notes cell says flame retardant, foam with skin. The shield is a 100% bi-laminate tape plus a 65% tinned-copper braid. The jacket is PVC, 0.043 in (1.1 mm), nominal diameter 0.315 in (8.00 mm), with a jacket OD tolerance of 0.010 in.

Construction and electrical rows from the Belden pages opened October 24, 2026.
Item98413079A
Title on the pageRS-485PROFIBUS DP
Pair24 AWG, 7x32, tinned copper22 AWG, solid, bare copper
Pair colorsWhite/blue stripe and blue/white stripeRed and green
Nominal jacket OD0.232 in (5.89 mm)0.315 in (8.00 mm)
Impedance120 Ohm150 Ohm
Maximum current2.1 A per conductor at 25°C, 10°C rise2.3 A per conductor at 25°C
UL voltage300 V (CM), 30 V (UL AWM 2919)300 V (CMG, PLTC), 600 V (AWM 20201)
Operating temperature-30°C to +80°C-30°C to +75°C

120 Ohm and 150 Ohm are the impedance cells

As of October 24, 2026, 9841 lists conductor DCR of 24 Ohm/1000ft (79 Ohm/km), capacitance of 12.8 pF/ft (42.0 pF/m) conductor to conductor and 23 pF/ft (75 pF/m) conductor to other, delay of 1.6 ns/ft, and velocity of 66%. Outer-shield DCR is 3.4 Ohm/1000ft (11 Ohm/km). At 1 MHz the nominal insertion loss is 0.6 dB/100ft. 3079A lists conductor DCR of 18.9 Ohm/1000ft (62.0 Ohm/km), inductance of 0.282 µH/ft (0.925 µH/m), and velocity of 78%. Outer-shield DCR is 5.2 Ohm/1000ft (17 Ohm/km). Nominal insertion loss is 0.27 dB/100ft at 0.2 MHz, 0.67 dB/100ft at 4 MHz, and 1.37 dB/100ft at 16 MHz. Those frequency rows are separate tables. A loss at 1 MHz on 9841 is not a reading of the 0.2 MHz row on 3079A.

The voltage line and the location line differ

As of October 24, 2026, 9841 lists UL temperature 80°C, minimum bend radius 2.5 in (64 mm) for stationary and installation use, maximum pull tension 72.3 lbs (32.8 kg), and weight 36 lbs/1000ft (54 kg/km). Environmental suitability is indoor. Flammability is UL 1685 UL Loading and IEC 60332-1-2. CPR is Euroclass Eca and UKCA Class Eca. NEC compliance is Article 800, CM. AWM compliance is AWM 2919. The other-standard cell says DMX-512. Plenum numbers named on the page are 82841 and 89841. The non-plenum number named on the page is 9841ZH. Those three product pages were not the source of the ratings in this guide. Page revision is 0.725, dated 02-25-2026.

As of October 24, 2026, 3079A lists UL temperature 75°C, minimum bend radius 2.4 in (61 mm) for stationary and installation use, maximum pull tension 50 lbs (23 kg), and weight 52 lbs/1000ft (77 kg/km). Environmental suitability is indoor, outdoor, and sunlight resistance. Flammability is UL 1685 FT4 Loading, FT4, IEEE 1202, and IEC 60332-1-2. CPR is Euroclass Eca and UKCA Class Eca. NEC compliance is Article 725, Article 800, CM, CMX-Outdoor, PLTC, and ITC. AWM compliance is AWM 20201. The suitable-applications cell names Profibus DP or PA, along with instrumentation and computer cable. The 150 Ohm cell remains the impedance printed for this cable. The notes call it Siemens Sinec L2 cable and name a CPE jacket as YR45047 and LSZH jackets as 3079T or YR44731. Those jacket pages were not opened. Page revision is 0.658, dated 02-26-2026.

The Modbus category page uses other rows

Belden's Modbus category page, opened October 24, 2026, does not list 9841. The table's Modbus Plus row is 24 AWG, 1 pair, described as RS485 paired cable, with a PDF link and no product number in the cell. The Modbus row is 22 AWG, 3 pair, standard modem drop cable, and the product link is 8777. The Modbus II row is 18 AWG, 1 coax, standard quad shield coax, and the product link is 3092A. Impedance and jacket for those links, including the high-temp, high-flex, and armor rows, are on the 8777 and 3092A page, from product pages opened October 25, 2026. A request for the one-pair 24 AWG RS-485 cable at 120 Ohm stays on 9841. The two-pair cable at that gauge and impedance is on the 9841 and 9842 page. The 22 AWG PLTC cable at 120 Ohm is on the 3105A and 9841 page.

What to copy onto the cable line

  • Part: 9841 or 3079A, from the page opened October 24, 2026.
  • Impedance: 120 Ohm on 9841, or 150 Ohm on 3079A.
  • Gauge and metal: 24 AWG stranded tinned copper, or 22 AWG solid bare copper.
  • Nominal jacket diameter and the UL voltage lines for that part.
  • Location: indoor on 9841, or indoor, outdoor, and sunlight resistance on 3079A.
  • For a Modbus category row, the system name on that table. 9841 is the RS-485 page.

RS-485 or PROFIBUS cable note

Name 9841 or 3079A and the impedance on that page.

This prepares a request. It does not send one.

Questions these pages answer

Is a 24 AWG RS-485 pair the same part as 3079A?

9841 is 24 AWG stranded tinned copper at 120 Ohm, as of October 24, 2026. 3079A is 22 AWG solid bare copper at 150 Ohm. The pair count is one on both pages. Gauge, metal, color, and impedance are different.

Which cable prints 30 V on the AWM line?

9841 prints 300 V (CM) and 30 V (UL AWM 2919), as of October 24, 2026. 3079A prints 300 V (CMG, PLTC) and 600 V (AWM 20201). The AWM style numbers are 2919 and 20201.

Does the 3079A applications cell make 150 Ohm a PA impedance?

The applications cell names Profibus DP or PA. The impedance cell on the same page is 150 Ohm. The PA comparison stays on the DP and PA page. PROFINET Type A is the 3079A and Type A page.

Sources

9841 construction, 120 Ohm, the 30 V AWM 2919 line, and the plenum numbers are from the 9841 page. 3079A construction, 150 Ohm, the 600 V AWM 20201 line, and the jacket notes are from the 3079A page. The Modbus category rows are from the Modbus cable category page. All three were opened October 24, 2026.