Industrial networking

Belden 3108A Three Pair or 3109A Four Pair

Use 3108A for three 22 AWG pairs at 4.2 A and 0.374 in. Use 3109A for four 22 AWG pairs at 2.7 A and 0.448 in.

Rust Belt Industrials · October 27, 2026 · 5 min read

On this page

Use Belden 3108A when the harsh-environment RS-485 cable is three 22 AWG pairs. As of October 27, 2026, that sheet lists a nominal jacket diameter of 0.374 in (9.50 mm), 120 Ohm, conductor DCR of 18.2 Ohm/1000ft, and 4.2 A per conductor at 30°C. Use Belden 3109A when the cable is four pairs. As of the same day, that sheet lists a nominal jacket diameter of 0.448 in (11.4 mm), 120 Ohm, conductor DCR of 14.7 Ohm/1000ft, and 2.7 A per conductor at 25°C. The April 2022 line card lists both as 22 AWG industrial PVC, CM/PLTC, for an industrial or other harsh environment, 3108A at 3 pair and 3109A at 4 pair. One pair and two pair at this gauge are 3105A and 3107A, on the 3105A and 3107A page.

The harsh table already separates 3 pair from 4 pair

As of October 27, 2026, the line card lists 3105A at 1 pair, 3106A at 1.5 pair, 3107A at 2 pair, 3108A at 3 pair, and 3109A at 4 pair, all SF/UTP, 22 AWG, industrial PVC, and CM/PLTC. The 3108A sheet and the 3109A sheet each print 300 V (CM, PLTC). The title on each says CM, PLTC, and oil resistant. A CPE direct-burial jacket at the same 3-pair count is 3108DB, on the 3108A and 3108DB page. The 24 AWG light-industrial 3-pair cable is 9843, on the 9843 and 9844 page.

Same insulation diameter, one more color pair

As of October 27, 2026, both sheets list 22 AWG (7x30) tinned copper, foam polyethylene insulation of 0.023 in (0.58 mm), a nominal insulation diameter of 0.075 in (1.9 mm), notes HDPE, a 100% bi-laminate tape, a 22 AWG (7x30) tinned-copper drain, a 65% tinned-copper braid, and a PVC jacket of 0.053 in (1.3 mm). 3108A colors are the blue, orange, and green stripe pairs. 3109A adds white/brown stripe and brown/white stripe. Neither sheet prints a jacket OD tolerance. Inductance on both is 0.225 µH/ft (0.738 µH/m).

22 AWG three-pair and four-pair rows from the sheets opened October 27, 2026.
Item3108A3109A
Line-card pair column34
Nominal jacket OD0.374 in (9.50 mm)0.448 in (11.4 mm)
Conductor DCR18.2 Ohm/1000ft14.7 Ohm/1000ft
Current4.2 A per conductor at 30°C2.7 A per conductor at 25°C
Outer-shield DCR3.576 Ohm/1000ft (11.73 Ohm/km)2.53 Ohm/1000ft (8.30 Ohm/km)
Maximum pull tension90 lbs (41 kg)100 lbs (45 kg)
CPR lineEuroclass EcaEuroclass Eca and UKCA Class Eca
Flammability extraNot printedFT1

The current cell changes temperature as well as amperes

As of October 27, 2026, both sheets list capacitance of 11 pF/ft (36 pF/m) conductor to conductor and 20.9 pF/ft (68.6 pF/m) conductor to other, impedance of 120 Ohm, velocity of 78%, and insertion loss of 0.5 dB/100ft at 1 MHz. Conductor DCR is 18.2 Ohm/1000ft on 3108A and 14.7 Ohm/1000ft on 3109A. Neither DCR cell prints a kilometer figure. Current is 4.2 A per conductor at 30°C on 3108A and 2.7 A per conductor at 25°C on 3109A. Those cells do not share a temperature. Outer-shield DCR is 3.576 Ohm/1000ft (11.73 Ohm/km) on 3108A and 2.53 Ohm/1000ft (8.30 Ohm/km) on 3109A. Voltage is 300 V (CM, PLTC) on both.

Oil and sunlight on both, FT1 on 3109A

As of October 27, 2026, both sheets list UL temperature 60°C, operating temperature -20°C to +60°C, and suitability indoor, outdoor, sunlight resistance, and oil resistance. Flammability on 3108A is UL 1685 UL Loading and IEC 60332-1-2. Flammability on 3109A adds FT1 to that list. NEC compliance is Article 725, Article 800, CM, PLTC. CEC compliance is CM. CPR on 3108A is Euroclass Eca. CPR on 3109A is Euroclass Eca and UKCA Class Eca. Both print UKCA Mark on the UK regulation line. Minimum bend radius is 4.488 in (114.0 mm) on 3108A and 5.5 in (140 mm) on 3109A. Maximum pull tension is 90 lbs (41 kg) on 3108A and 100 lbs (45 kg) on 3109A. Bulk weight is 63 lbs/1000ft on 3108A and 82 lbs/1000ft on 3109A. Neither weight cell prints a kilogram.

Both notes say oil resistance passes Oil Res II per UL 1277, Table 10.17, as of October 27, 2026. The CPE note names YR45287 on 3108A and YR44768 on 3109A. Those pages were not opened. 3108DB is a separate CPE direct-burial sheet. YR45287 stays the number printed in the 3108A note. Page revision is 0.552, dated 02-20-2026, on both sheets. Put-ups are black reels at 1,000 ft, 2,000 ft, and 5,000 ft. Footnote C, crate reel put-up, is on the 1,000 ft and 2,000 ft rows of each sheet. The 5,000 ft row does not print C.

What to copy onto the cable line

  • Part: 3108A or 3109A, from the sheet opened October 27, 2026.
  • Pairs: three, or four, with the color list from that sheet.
  • Nominal diameter: 0.374 in (9.50 mm), or 0.448 in (11.4 mm).
  • Current: 4.2 A per conductor at 30°C, or 2.7 A per conductor at 25°C.
  • Conductor DCR: 18.2 Ohm/1000ft, or 14.7 Ohm/1000ft.
  • Listing: 300 V (CM, PLTC), plus the CPR line from that sheet.

3108A or 3109A note

Name three pairs or four pairs, and copy the current cell with its temperature.

This prepares a request. It does not send one.

Questions these sheets answer

Does four pairs keep the 4.2 A cell?

3108A prints 4.2 A per conductor at 30°C, as of October 27, 2026. 3109A prints 2.7 A per conductor at 25°C. The impedance cell stays 120 Ohm. The current cell changes the ampere and the temperature.

Does 14.7 Ohm replace 18.2 Ohm?

Copy 18.2 Ohm/1000ft for 3108A and 14.7 Ohm/1000ft for 3109A, as of October 27, 2026. The sheets print those two cells.

Does the 3108A flammability line include FT1?

FT1 is on the 3109A flammability cell, as of October 27, 2026. The 3108A cell lists UL 1685 UL Loading and IEC 60332-1-2. Copy the cell that belongs to the part.

Sources

Pair count, diameter, current, conductor DCR, and the CPR line are from the Belden 3108A and 3109A technical data sheets. The 3 pair and 4 pair labels are from the Belden RS-485 line card dated April 2022. All three were opened October 27, 2026. YR45287, YR44768, and 3109DB were not used for the cells on this page.