Power connections
6101 Aluminum Busbar or 1350
Use 1350-H111 when the extruded bar is 61.0% IACS and 8.5 ksi. Use 6101-T6 at 55.0% IACS and 29.0 ksi through 0.500 inch, or 6101-T64 at 59.5% IACS when the bar has to bend.
On this page
Use 1350-H111 when the extruded bar can stay at 8.5 ksi minimum ultimate strength and 61.0% IACS. Use 6101-T6 when the thickness is 0.125 inch to 0.500 inch and the bar needs 29.0 ksi ultimate, 25.0 ksi yield, and 55.0% IACS. Use 6101-T64 when the thickness is 0.125 inch to 1.000 inch and the order wants the highest 6101 conductivity on these sheets, 59.5% IACS, at 15.0 ksi ultimate and 8.0 ksi yield. As of November 8, 2026, those strength and conductivity cells match on the Aluminum Association Table 16.3 and on Hydro's 6101 data sheet. Ampacity for a fixed flat size in 6101, without a temper split, stays on the aluminum ampacity page.
Hydro says 6101 trades a small amount of conductivity for strength against 1350
Hydro's sheet, revision 2019/01, opened November 8, 2026, says alloy 6101 is a heat-treatable wrought alloy for moderate strength and electrical conductivity. It says 6101 is similar to 6063, with chemistry changes that raise conductivity, and that it is slightly lower in conductivity than alloy 1350 and offers greater strength. It says bus bar is available with sharp corners or radius corners, and that the alloy satisfies ASTM B317 for the tempers on the sheet. Table 16.3 is the page that prints the 1350-H111 numbers: for extruded rod, bar, tube, pipe, and structural profiles, all thicknesses, minimum ultimate tensile strength 8.5 ksi, minimum yield 3.5 ksi, and minimum electrical conductivity 61.0% IACS at 68°F. Hydro does not print that 61.0% cell or the 8.5 ksi cell. Copy 1350's numbers from Table 16.3. Copy the sentence that 6101 is slightly lower in conductivity, and greater in strength, from Hydro.
Table 16.3 also lists rolled 1350-H12 bar, 0.125 inch to 1.000 inch, at 12.0 ksi ultimate, 8.0 ksi yield, and 61.0% IACS. Sawed-plate 1350-H112 is 11.0 ksi and 6.0 ksi yield from 0.125 inch to 0.499 inch, 10.0 ksi and 4.0 ksi from 0.500 inch to 1.000 inch, and 9.0 ksi and 3.5 ksi from 1.001 inch to 1.500 inch, all at 61.0% IACS. Sheet 1350-O, 0.006 inch to 0.125 inch, is 8.0 ksi minimum and 14.0 ksi maximum ultimate, at 61.8% IACS. An extruded bar and a rolled bar are different product lines. The 61.0% figure is shared. The strength is not.
Each 6101 temper pairs a thickness band with strength and conductivity
Hydro's temper definitions, as of November 8, 2026, say T6 is solution heat-treated and artificially aged to maximum mechanical property levels. T61 is an over-aged temper with higher conductivity and lower mechanical properties than T6. T63 is between T6 and T61 in conductivity. T64 is the highest conductivity and the temper for maximum formability, described as partially annealed. T65 is medium strength and conductivity, with a controlled range of tensile and yield strength for bending reproducibility. Table 16.3 and the Hydro property table print the same minimums for the standard tempers below. Hydro also prints the ultimate and yield in MPa. Table 16.3 prints ksi.
| Temper | Thickness | Ultimate | Yield | IACS |
|---|---|---|---|---|
| 1350-H111, extruded | All | 8.5 ksi | 3.5 ksi | 61.0% |
| 6101-T6 | 0.125 to 0.500 in | 29.0 ksi | 25.0 ksi | 55.0% |
| 6101-T61 | 0.125 to 0.749 in | 20.0 ksi | 15.0 ksi | 57.0% |
| 6101-T61 | 0.750 to 1.499 in | 18.0 ksi | 11.0 ksi | 57.0% |
| 6101-T61 | 1.500 to 2.000 in | 15.0 ksi | 8.0 ksi | 57.0% |
| 6101-T63 | 0.125 to 1.000 in | 27.0 ksi | 22.0 ksi | 56.0% |
| 6101-T64 | 0.125 to 1.000 in | 15.0 ksi | 8.0 ksi | 59.5% |
| 6101-T65 | 0.125 to 0.749 in | 25.0 to 32.0 ksi | 20.0 to 27.0 ksi | 56.5% |
Hydro prints a flatwise bend radius for bus bar. Table 16.3 does not
Hydro's flatwise bending radii, as of November 8, 2026, are for bus bar only, bent at room temperature through 90 degrees to the minimum inside radius, without cracking and without slivers. The note limits the radii to widths through 6 inches for T6, T61, T63, and T65, and to widths through 12 inches for T64. T6 from 0.125 inch to 0.375 inch is 2.0 times thickness. T6 from 0.376 inch to 0.500 inch is 2.5 times thickness. T64 and T64P from 0.125 inch to 0.750 inch are 1.0 times thickness, and from 0.751 inch to 1.000 inch are 2.0 times thickness. T61 from 0.125 inch to 0.500 inch is 1.0 times thickness. T63 from 0.125 inch to 0.375 inch is 1.0 times thickness, from 0.376 inch to 0.500 inch is 1.5 times thickness, and from 0.501 inch to 1.000 inch is 2.5 times thickness.
A T6 bar at 0.250 inch uses a 2.0 times thickness inside radius on that Hydro table, which is 0.500 inch, and it is also the temper at 29.0 ksi and 55.0% IACS. A T64 bar at 0.250 inch uses 1.0 times thickness, 0.250 inch, and it is the temper at 15.0 ksi and 59.5% IACS. Table 16.3 does not print a radius. Storm's conversion sheet, used on the ampacity page, says aluminum can crack at a very tight radius and does not print a radius in inches. The inch radius on a 6101 bus bar comes from Hydro's table, for the temper and the thickness band on that row.
Hydro's special tempers are not rows in Table 16.3
Hydro marks T61P, T64P, and OP as special tempers that are not recognized by the Aluminum Association. As of November 8, 2026, T61P from 0.125 inch to 0.749 inch keeps 20.0 ksi ultimate and 57.0% IACS, and the yield is a range, 15.0 ksi to 22.0 ksi. T64P from 0.125 inch to 1.000 inch keeps 15.0 ksi ultimate and 59.5% IACS, and the yield is 8.0 ksi to 15.0 ksi. OP from 0.125 inch to 1.000 inch is a maximum of 19.0 ksi ultimate and a maximum of 8.0 ksi yield, at 59.5% IACS. Table 16.3 does not list T61P, T64P, or OP. A purchase order that cites the Aluminum Association table uses T6, T61, T63, T64, T65, or the 1350 tempers on that table. A purchase order that cites Hydro's special temper uses the Hydro row and says it is the unregistered temper.
Hydro also prints chemistry and physical constants for 6101. As of November 8, 2026, density is 0.097 lb/in³, the melting range is 1,150°F to 1,210°F, and the average coefficient of thermal expansion from 68°F to 212°F is 13.0 x 10^-6 in/in°F. Silicon is 0.30 to 0.7 percent, magnesium is 0.35 to 0.8 percent, and iron is 0.50 percent maximum. Thermal conductivity at 77°F is 1,510 BTU-in/ft²hr°F for T6, T63, and T65, 1,540 for T61, and 1,570 for T64. Table 16.4 on the Aluminum Association sheet converts a conductivity to resistivity. At 55.0% IACS the volume resistivity is 18.856 ohm-circular mil/ft and 1.2341 microhm-in. At 59.5% IACS it is 17.430 ohm-circular mil/ft and 1.1408 microhm-in. At 61.0% IACS it is 17.002 ohm-circular mil/ft and 1.1128 microhm-in. Those resistivity cells are the conversion table. They are not a second conductivity test.
What to copy onto the bar line
- Alloy and temper: 1350-H111, or 6101-T6, T61, T63, T64, or T65, from the sheets opened November 8, 2026.
- Thickness band that selects the strength row.
- Minimum ultimate, minimum yield, and minimum percent IACS at 68°F.
- Product form: extruded, rolled bar, or sawed plate, because 1350 strength changes with the form.
- Flatwise bend radius from Hydro, when the bar is 6101 bus bar and the width is inside the 6 inch or 12 inch note.
- Special temper name, T61P, T64P, or OP, only when the order is the Hydro sheet and not Table 16.3.
Questions these two sheets answer
Which 6101 temper is 55.0% IACS?
6101-T6, 0.125 inch to 0.500 inch, at 29.0 ksi ultimate and 25.0 ksi yield, as of November 8, 2026. T64 is 59.5% IACS. T61 is 57.0% IACS. Extruded 1350-H111 is 61.0% IACS.
What inside radius does Hydro print for a 0.250 inch T6 bar?
2.0 times thickness for T6 from 0.125 inch to 0.375 inch, as of November 8, 2026. At 0.250 inch that radius is 0.500 inch. The same thickness in T64 is 1.0 times thickness.
Does 61.0% IACS mean 8.5 ksi?
On extruded 1350-H111, yes, as of November 8, 2026. Rolled 1350-H12 at 61.0% IACS is 12.0 ksi ultimate. The conductivity cell is shared. The strength cell follows the product form.
Sources
1350 strength and conductivity, and the 6101 temper minimums that match Hydro, are from Aluminum Association Table 16.3, the May 2009 sheet. Hydro's 6101 sheet, revision 2019/01, repeats those 6101 minimums, prints the bend radii, and states that 6101 is slightly lower in conductivity than 1350 and greater in strength. Both were opened November 8, 2026.