Power connections
Aluminum Busbar Ampacity or Copper for the Same Size
For one flat size, read the C110 copper columns or the 6101 aluminum columns on Storm's conversion sheet. A larger aluminum section is a separate choice.
On this page
For the same flat size, use the copper C110 columns when the bar is copper and the 6101 columns when the bar is aluminum. As of November 7, 2026, Storm's conversion sheet lists a 1/4 inch by 4 inch copper bar at 1250 A, 1700 A, and 1950 A for a 30°C, 50°C, and 65°C rise, and the 6101 bar of that size at 700 A, 952 A, and 1092 A. Copper weight on that row is 3.860 lb/ft on the conversion sheet and 3.86 lb/ft on the C11000 chart opened the same day. Aluminum weight on the conversion sheet is 1.170 lb/ft. A 1/4 inch by 1 inch row is 400 A, 530 A, and 620 A in copper, and 224 A, 297 A, and 347 A in 6101. Growing the aluminum section so its rise matches a smaller copper bar is the separate method on the copper and aluminum page.
The conversion sheet pairs one size in both metals
The conversion sheet opened November 7, 2026 is titled Converting Copper to Aluminum using an Ampacity Chart. Each row is one flat bar size. The copper block is labeled Copper C110. The aluminum block is labeled Aluminum 6101. Both blocks print 60 Hz ampacity for a 30°C rise, a 50°C rise, and a 65°C rise, plus weight per foot and DC resistance at 20°C in microhms per foot. The three rows below are rows whose copper amps also appear on Storm's C11000 chart, opened the same day. A 1/16 inch by 1/2 inch copper bar is 103 A, 136 A, and 157 A on both pages. The conversion sheet lists that 6101 size at 58 A, 76 A, and 88 A, at 0.037 lb/ft, against 0.121 lb/ft for the copper. DC resistance on that row is 264 microhms per foot for copper and 494 microhms per foot for 6101.
As of November 7, 2026, the 1/4 inch by 1 inch copper row is 0.250 square inch, 318 thousand circular mils, 0.966 lb/ft, and 32.9 microhms per foot, at 400 A, 530 A, and 620 A. The 6101 row is 0.293 lb/ft and 62 microhms per foot, at 224 A, 297 A, and 347 A. The 1/4 inch by 4 inch copper row is 1 square inch, 1270 thousand circular mils, and 8.23 microhms per foot, at 1250 A, 1700 A, and 1950 A. The 6101 row is 1.170 lb/ft and 15 microhms per foot, at 700 A, 952 A, and 1092 A. The C11000 chart prints the copper weight for the 1/4 inch by 4 inch row as 3.86 lb/ft. The conversion sheet prints 3.860 lb/ft. Those two copper weights are the same figure. The aluminum weight is only on the conversion sheet.
| Size | Metal | 30°C rise | 50°C rise | 65°C rise | Weight | DC resistance at 20°C |
|---|---|---|---|---|---|---|
| 1/16 in by 1/2 in | C110 copper | 103 A | 136 A | 157 A | 0.121 lb/ft | 264 microhms/ft |
| 1/16 in by 1/2 in | 6101 aluminum | 58 A | 76 A | 88 A | 0.037 lb/ft | 494 microhms/ft |
| 1/4 in by 1 in | C110 copper | 400 A | 530 A | 620 A | 0.966 lb/ft | 32.9 microhms/ft |
| 1/4 in by 1 in | 6101 aluminum | 224 A | 297 A | 347 A | 0.293 lb/ft | 62 microhms/ft |
| 1/4 in by 4 in | C110 copper | 1250 A | 1700 A | 1950 A | 3.860 lb/ft on the sheet | 8.23 microhms/ft |
| 1/4 in by 4 in | 6101 aluminum | 700 A | 952 A | 1092 A | 1.170 lb/ft | 15 microhms/ft |
The copper chart states the installation, and the conversion sheet states a limit
As of November 7, 2026, the C11000 chart says the ampacities are for bus bars having an emissivity of 0.4, observed on samples exposed for 60 days in an industrial environment. The footnote says the values apply to typical in-service conditions: indoors, 40°C ambient, a horizontal run on edge, and free from external magnetic influences. The copper ampacity page is the page that walks the 30°C, 50°C, and 65°C columns for copper alone. The conversion sheet does not reprint the emissivity sentence or the 40°C ambient sentence on the aluminum block. Its note says ratings depend upon configuration, air flow, ambient temperature, and similar conditions, that the values depicted are an approximation, and that controlled testing is always required to validate.
The conversion sheet credits the copper column to the Copper Development Association and the aluminum column to an Aluminum Association file. The copper amps in the table above were checked against Storm's own C11000 chart. Copy an aluminum amp from the conversion sheet's 6101 cell. The sheet also lists forming, electroplating, and configuration as other considerations. It says aluminum has a tendency to crack with a very tight radius, and it does not print a radius. It names white rust on aluminum and oxidation as plating issues. It names vertical or horizontal configuration as a separate line from the ampacity cells.
The aluminum page names 6101, weight, and expansion
Storm's aluminum page, opened November 7, 2026, says the most commonly used 6101 aluminum alloy offers 56 percent of copper's conductivity at half the weight of copper. The conversion sheet is the page that prints pound-per-foot figures for named sizes. Half the weight is the alloy page's general line. For the 1/4 inch by 4 inch row, 1.170 lb/ft against 3.860 lb/ft is the pair the conversion sheet prints. The aluminum page also says aluminum's thermal expansion and contraction is 42 percent higher than copper, and that silver or tin electroplating for aluminum joints is available in-house. It says Storm can provide torque and washer information and does not print a torque value on that page.
The alloy page's temperature-rise paragraph says aluminum conducts at a lower level than copper and that a larger surface area is the compensation it often recommends. That is the section-growth method. This page keeps the flat size fixed and reads the lower 6101 current. A drawing that changes 1/4 inch by 4 inch copper into 1/4 inch by 4 inch 6101 keeps the envelope and takes the 700 A, 952 A, or 1092 A cell. A drawing that must hold the copper current uses the section-growth note on the copper and aluminum page.
What to copy onto the bar line
- Metal: C110 copper or 6101 aluminum, from the conversion sheet opened November 7, 2026.
- Size: thickness and width. The rows checked here are 1/16 inch by 1/2 inch, 1/4 inch by 1 inch, and 1/4 inch by 4 inch.
- Rise: 30°C, 50°C, or 65°C, and the amp in that cell.
- Weight and DC resistance at 20°C from the same row, when the request needs them.
- Installation: the C11000 chart's indoor, 40°C ambient, horizontal on edge line applies to the copper chart. The conversion sheet says the values are an approximation and that testing has to validate them.
- A larger aluminum section, when the current has to match copper, stays on the copper and aluminum page.
Questions these Storm pages answer
Does the same size carry the same current in 6101?
On the rows checked November 7, 2026, it does not. A 1/4 inch by 4 inch bar is 1250 A in C110 and 700 A in 6101 at a 30°C rise. The 50°C cells are 1700 A and 952 A. The 65°C cells are 1950 A and 1092 A.
Which weight goes with the 1/4 inch by 1 inch bar?
As of November 7, 2026, that copper row is 0.966 lb/ft on both the conversion sheet and the C11000 chart. The 6101 row is 0.293 lb/ft on the conversion sheet. The alloy page's half-weight sentence is the general line, and this row is the sized line.
What bend radius does the conversion sheet allow for aluminum?
The sheet says aluminum has a tendency to crack with a very tight radius, as of November 7, 2026. It does not print a radius in inches.
Sources
Paired amps, weights, and DC resistance are from Storm's copper-to-aluminum conversion sheet. The matching copper amps, the 0.4 emissivity line, and the 40°C ambient footnote are from Storm's C11000 chart. The 56 percent conductivity line, the half-weight line, and the 42 percent expansion line are from Storm's aluminum busbar page. All three were opened November 7, 2026.