Power connections
Silver Plated Copper Busbar or Tin
On ABB medium-voltage gear, use silver on a sliding contact at 10.0 to 20.0 micrometers, and tin where hydrogen sulfide is present or the bar is the ground bus, at 3.0 to 8.0 micrometers.
On this page
Use silver plate when the ABB medium-voltage contact slides, and use tin plate when that note's environment contains hydrogen sulfide or the bar is the ground bus on galvanized steel. As of November 8, 2026, ABB technical note 1VAL0009-TN Rev A, dated 8/8/2024, lists sliding silver at 10.0 to 20.0 micrometers and static silver at 1.27 to 3.00 micrometers, both ASTM B700-08, Class N, Type 1, Grade D. Tin on that note is ASTM B545-97(2009), Class B, matte, at 3.0 to 8.0 micrometers. A silver-surfaced or tin-surfaced bus joint is a 65°C rise and 105°C total. An unplated copper-to-copper joint is a 30°C rise and 70°C total. Storm's class thickness for tin, and electroless nickel, stay on the tin and nickel page.
Plated joints share one rise. Unplated joints use the lower rise
Table 1 of the ABB note, opened November 8, 2026, is titled for bus and connections in medium-voltage switchgear assemblies. Buses and connections with unplated copper-to-copper joints are a 30°C rise and a 70°C total. Buses and connections with silver-surfaced or equivalent joints are a 65°C rise and a 105°C total. Buses and connections with tin-surfaced or equivalent joints are the same 65°C rise and 105°C total. Unplated copper-to-copper connections to insulated cables are 30°C and 70°C. Silver-surfaced connections to insulated cables are 45°C and 85°C. Tin-surfaced connections to insulated cables are 45°C and 85°C. Note 2 says the cable connections are based on 90°C insulated cable. Note 1 says that when a connection has different platings, the rise and the limit follow the lowest rating in the table.
Silver and tin share the bus-joint rise on this table, and they share the cable-connection rise. The contact type and the atmosphere, in the paragraphs under the table, pick the finish. An unplated joint is the row at 30°C on the bus and 30°C on the cable connection, against 65°C and 45°C for the plated rows. The note says the IEEE C37.20.2 allowance for unplated copper requires more copper for the same continuous current, because the rise limit is lower. The extra copper section is not printed.
| Connection | Rise limit | Total limit |
|---|---|---|
| Unplated copper-to-copper bus joint | 30°C | 70°C |
| Silver-surfaced bus joint | 65°C | 105°C |
| Tin-surfaced bus joint | 65°C | 105°C |
| Unplated connection to insulated cable | 30°C | 70°C |
| Silver-surfaced connection to insulated cable | 45°C | 85°C |
| Tin-surfaced connection to insulated cable | 45°C | 85°C |
Sliding contacts take the thicker silver. Hydrogen sulfide and the ground bus take tin
The ABB note, as of November 8, 2026, says standard tested designs use silver on phase buses and connections. It says silver suits an indoor, climate-controlled room, forms a hard surface for sliding contacts such as a withdrawable breaker, and tarnishes while keeping nearly the same conductivity. It says silver will corrode where hydrogen sulfide is present. For hydrogen sulfide or other caustic substances, it recommends tin on all phase buses, bus joints, and insulated-cable termination pads. It says tin is much softer than silver and cannot be used on primary sliding contacts. For those sliding contacts in that environment, it recommends contact lubricating grease on the silver surfaces. All ground bus in this switchgear is tin-plated, because the enclosure metal is galvanized steel. ABB says it manufactures phase and ground bus from high-conductivity copper and does not offer aluminum phase or ground bus.
Thickness stays with the duty. As of November 8, 2026, sliding silver is 10.0 to 20.0 micrometers. Static silver is 1.27 to 3.00 micrometers. Both use ASTM B700-08, Class N, Type 1, Grade D. Tin is 3.0 to 8.0 micrometers, ASTM B545-97(2009), Class B, matte, applied electrolytically. The bus is pre-plated, then cut and punched, and the note says the inside of the holes and the cut edge are no longer plated after that. It says this does not change the contact-surface conductivity. A drawing that needs plating inside a punched hole has to say so. The note's process leaves that surface bare.
Storm uses tin or silver on a bolted joint, and nickel when the joint is welded
Storm's plating design guide, opened November 8, 2026, lists bright tin, matte tin, electrolytic nickel, electroless nickel, silver including ASTM B700 options, tin-lead, and lead as in-house finishes for copper and aluminum busbar. It says bolted or clamped joints can be tin, tin-lead, silver, or nickel, and that tin and silver are the finishes it names where low contact resistance matters. It says soldered connections can use tin or tin-lead, and that silver and nickel are also suitable with the right process. It says welded connections generally accept nickel, and that tin and silver are typically not the finish where the joint will be welded. A Storm bar that will be welded copies nickel. A Storm bar that will be bolted, and that needs the low contact resistance the guide names, copies tin or silver.
The tin section says the coat is soft enough to deform under bolt pressure and soft enough to scratch, and that it is the wrong finish for sliding or abrasive contacts. ABB's sentence says tin cannot be used on a primary sliding contact. Bright tin, on the Storm guide, has a higher whisker risk and a shinier look. Matte tin has a lower whisker tendency and a duller surface that shows fingerprints. ABB's tin callout is matte Class B. A Storm request that names whisker risk copies matte tin, nickel, or tin-lead. The guide says lead in tin-lead inhibits whisker growth. Silver, on the Storm guide, is the finish for very low contact resistance and high temperature. It says silver tarnish is usually cosmetic in power work because silver oxide remains conductive. ABB's sentence says tarnish keeps nearly the same conductivity, and that hydrogen sulfide corrodes silver. Copy ABB's hydrogen-sulfide rule when the gear is the equipment in that note. Copy Storm's oxide sentence when the bar is a Storm plating order. Each sentence stays with the page that printed it.
What to copy onto the finish line
- Equipment: ABB medium-voltage metal-clad note 1VAL0009-TN Rev A, or a Storm plating order, as opened November 8, 2026.
- ABB silver, sliding: ASTM B700-08, Class N, Type 1, Grade D, 10.0 to 20.0 micrometers.
- ABB silver, static: the same class, 1.27 to 3.00 micrometers.
- ABB tin: ASTM B545-97(2009), Class B, matte, 3.0 to 8.0 micrometers, for hydrogen sulfide, caustic conditions, or the ground bus.
- Rise: 65°C and 105°C total for a plated bus joint, or 30°C and 70°C total for an unplated copper-to-copper joint.
- Cable connection: 45°C and 85°C for silver or tin, based on 90°C insulated cable.
- Storm joint: tin or silver for a bolted joint that needs low contact resistance, and nickel when the joint will be welded.
- Holes: ABB's pre-plated bar leaves the punched hole and the cut edge unplated.
Questions these two plating pages answer
Does silver run hotter than tin on the ABB table?
On the bus joint, both are a 65°C rise and 105°C total, as of November 8, 2026. On the cable connection, both are a 45°C rise and 85°C total. The unplated joint is the 30°C row.
Which silver thickness is the sliding contact?
10.0 to 20.0 micrometers, as of November 8, 2026. Static silver on the same note is 1.27 to 3.00 micrometers. Both are ASTM B700-08, Class N, Type 1, Grade D.
Can the tin line be welded?
Storm's guide says tin and silver are typically not the finish for a welded joint, as of November 8, 2026. Nickel is the finish that guide names for welding. ABB's note does not describe a welded phase joint.
Sources
Rise limits, micrometers, ASTM callouts, the hydrogen-sulfide rule, and the ground-bus tin rule are from ABB note 1VAL0009-TN Rev A. Bolted, soldered, and welded finish lines, and the bright-tin and matte-tin whisker lines, are from Storm's busbar plating design guide. Both were opened November 8, 2026.