Skip to the guide

Power connections

Flexible Busbar or Cable at the Same Current

At a 50°C rise, the brochure pairs a smaller Flexibar section with a larger cable section: 40 mm² with 95 mm² at 250 A, 160 mm² with 300 mm² at 630 A, and 300 mm² with 555 mm² at 1,000 A.

Rust Belt Industrials · November 8, 2026 · 7 min read

On this page

Use one Flexibar when the brochure's 50°C comparison is the section on the drawing. Use the cable build when the drawing names that larger copper section for the same current. As of November 8, 2026, nVent brochure P1349W-USEN pairs one Flexibar of 2 x 20 x 1 mm, 40 mm², with one 95 mm² cable at 250 A, and calls the Flexibar 58% smaller. It pairs one Flexibar of 5 x 32 x 1 mm, 160 mm², with two 150 mm² cables, 300 mm² together, at 630 A, and calls the Flexibar 47% smaller. It pairs one Flexibar of 6 x 50 x 1 mm, 300 mm², with three 185 mm² cables, 555 mm² together, at 1,000 A, and calls the Flexibar 46% smaller. The sleeve compound is a separate choice on the jacket page.

Each row is one current, one Flexibar, and one cable build

The skin-effect comparison opened November 8, 2026 says the figures are representative to scale and that Flexibar intensity and cable intensity are based on a conductor temperature rise of 50°C. The three constructions sit next to those currents. 2 x 20 x 1 mm is 40 mm², which is the Flexibar section beside 250 A and beside the 95 mm² cable. 5 x 32 x 1 mm is 160 mm², which is the Flexibar section beside 630 A and beside 300 mm² of cable. 6 x 50 x 1 mm is 300 mm², which is the Flexibar section beside 1,000 A and beside 555 mm² of cable. Two 150 mm² cables are 300 mm². Three 185 mm² cables are 555 mm². One 95 mm² cable is the first cable line.

The percent lines follow those three pairs. As of November 8, 2026, 40 mm² against 95 mm² is the 58% smaller line, 160 mm² against 300 mm² is the 47% smaller line, and 300 mm² against 555 mm² is the 46% smaller line. The brochure prints those percents as the section reduction. It does not print a weight reduction or a price. A request copies the current, the Flexibar layer count, and the cable count together. A request that says only 630 A has not chosen 5 x 32 x 1 mm or two 150 mm² cables.

50°C comparison in the Flexibar brochure opened November 8, 2026. Cable copper is the sum of the cable sections named on that comparison.
Current at 50°C riseFlexibarFlexibar sectionCable buildCable copperSmaller line
250 A2 x 20 x 1 mm40 mm²1 x 95 mm²95 mm²58%
630 A5 x 32 x 1 mm160 mm²2 x 150 mm²300 mm²47%
1,000 A6 x 50 x 1 mm300 mm²3 x 185 mm²555 mm²46%

The brochure states a skin depth for round copper and a surface advantage for the flat stack

The same section, as of November 8, 2026, says skin effect concentrates alternating current near the surface of a conductor. It says that at 60 Hz in copper, the skin depth is about 8.5 mm for a round conductor. It says Flexibar's rectangular geometry has a low skin-effect ratio because the width-to-thickness ratio is greater than a cable's, and that the same cross section has a greater surface for cooling and a more uniform current density. The 8.5 mm figure is the round-conductor sentence. It is not a thickness limit printed on the 2 x 20 x 1 mm, 5 x 32 x 1 mm, or 6 x 50 x 1 mm rows. Those rows are 1 mm thick layers. The comparison still uses the 50°C rise, not a separate skin-effect ampacity column.

A current-density graphic later in the brochure compares cable, bare copper bar, and Flexibar at 50/60 Hz. One graphic is at 70°C working temperature, a 30°C rise, under IEC 61439-1. Another is at 75°C working temperature, a 45°C rise, under UL, and that second graphic names cable and Flexibar. The graphics do not print a readable table of amperes per square millimeter. The three rows above are the comparison that prints a current next to two sections.

Cable bend radius uses a multiplier. The brochure does not give Flexibar a matching multiplier

The bend-radius section, opened November 8, 2026, says Flexibar is made of copper layers and requires less bending space than cable, and that Flexibar has no strict minimum bending radius constraint. The cable chart on the same page is labeled an overview, and it says the cable manufacturer's data should be checked. Single or multiple conductor cables with no metallic shielding use 8 times the overall cable diameter. A single conductor cable with metallic shielding uses 12 times the overall cable diameter. Multiple conductor cables with individually shielded conductors use 12 times the individual cable diameter or 7 times the overall cable diameter, whichever is greater. The brochure attributes that chart to NEC Articles 300-34, 334-11, and 336-16, and to Appendix H of ICEA S-66-524 and ICEA S-68-516.

A Flexibar request does not copy the 8-times or 12-times multiplier. Those multipliers are the cable lines. A cable request copies the multiplier that matches the shield, and then checks the cable maker's own radius. The brochure also says a twist along a Flexibar should be 90 degrees or less, over a length of 3 to 4 times the busbar width, and not less than 2.5 times that width. It says the part should not be twisted more than 100 degrees. That twist length is a Flexibar forming note. It is not a cable bend radius.

The 50°C comparison is not the IEC or UL rise table

The IEC and UL ampacity tables are a different part of the same brochure, and they are the subject of the current page. As of November 8, 2026, the 5 x 32 x 1 mm section on this comparison is 160 mm² at 630 A for a 50°C rise, set beside two 150 mm² cables. The IEC table's 50°C cell for 5 x 32 x 1 mm is the cell on the current page, and the brochure's own parallel example there uses 640 A. This comparison prints 630 A. Both numbers are in the brochure. Copy 630 A when the request is this cable comparison. Copy the IEC or UL cell when the request names that table. The jacket page is where Advanced, Standard, and Summum temperatures are copied. 250 A, 630 A, and 1,000 A are the comparison currents, and the brochure does not label them Advanced, Standard, or Summum.

What to copy onto the conductor line

  • Comparison: the 50°C cable comparison in P1349W-USEN, opened November 8, 2026.
  • Current: 250 A, 630 A, or 1,000 A.
  • Flexibar: 2 x 20 x 1 mm, 5 x 32 x 1 mm, or 6 x 50 x 1 mm, with 40 mm², 160 mm², or 300 mm².
  • Cable: 1 x 95 mm², 2 x 150 mm², or 3 x 185 mm².
  • Smaller line that belongs to that pair: 58%, 47%, or 46%.
  • Cable bend multiplier, when the conductor is cable: 8 times, 12 times, or the greater of 12 times the individual diameter and 7 times the overall diameter.
  • Sleeve name, when the conductor is Flexibar, from the jacket page.

Flexibar or cable note

Name the 50°C current. Copy the Flexibar section or the cable build from that row.

This prepares a request. It does not send one.

Questions this comparison answers

Is 630 A the IEC 50°C cell?

On this comparison, 630 A is the 50°C current beside 5 x 32 x 1 mm and two 150 mm² cables, as of November 8, 2026. The IEC table's 50°C example for that section is printed as 640 A on the current page. Copy the cell the drawing names.

What Flexibar sits beside one 95 mm² cable?

2 x 20 x 1 mm, 40 mm², at 250 A, as of November 8, 2026. The brochure calls that Flexibar 58% smaller than the 95 mm² cable.

Does Flexibar use the 12-times cable radius?

The 12-times line is for a single conductor cable with metallic shielding, as of November 8, 2026. The brochure says Flexibar has no strict minimum bending radius constraint, and it says to check the cable maker for the cable radius.

Sources

The 250 A, 630 A, and 1,000 A pairs, the 58%, 47%, and 46% lines, the 8.5 mm skin depth, and the cable bend multipliers are from nVent ERIFLEX brochure P1349W-USEN. It was opened November 8, 2026.