Power connections

Flexibar Advanced, Flexibar Standard, or Flexibar Summum

Use Flexibar Advanced for the halogen-free TPE sleeve at 115°C. Use Flexibar Standard for PVC at 105°C. Use Flexibar Summum for silicone at 280°C.

Rust Belt Industrials · November 8, 2026 · 6 min read

On this page

Use Flexibar Advanced when the sleeve is the halogen-free TPE compound and the working temperature is -50°C to 115°C. Use Flexibar Standard when the sleeve is PVC and the working temperature is -50°C to 105°C. Use Flexibar Summum when the sleeve is silicone and the working temperature is -50°C to 280°C. As of November 8, 2026, nVent brochure P1349W-USEN lists Advanced and Standard at a nominal voltage of 1,000 VAC and 1,500 VDC under UL, CSA, and IEC, and Summum at 1,000 VAC and 1,500 VDC under IEC. Advanced insulation is 1.8 mm thick. Standard and Summum insulation are 2 mm thick. Rise current for a named section stays on the IEC and UL page.

The brochure assigns one compound, one finish, and one temperature to each name

The specifications block opened November 8, 2026 names the conductor as electrolytic copper Cu-ETP at the purity printed 99,9%, on all three rows. Maximum resistivity at 20°C is printed once in that block as 0.017241 ohms.mm²/m. Dielectric strength is printed once as 20 kV/mm. Flammability is UL 94 V-0, and the glow-wire test is IEC 60695-2-11 at 960°C. The later flame section says all Flexibar carry UL 94 V-0, and that Standard and Advanced passed the glow-wire test at 960°C with burning or glow time of 30 seconds or less, with the paper and wood undamaged.

Finish is the column that separates the copper surface. Advanced is tinned. Standard is tinned or plain. Summum is plain. Typical insulation elongation is greater than 500% for Advanced, greater than 370% for Standard, and greater than 400% for Summum. Certification details list UL 67, UL 758, and CSA 90005 for Advanced and for Standard. The Summum certification cell in that block is a dash. A drawing that needs UL 67 or UL 758 copies Advanced or Standard. A drawing that needs 280°C copies Summum and does not copy those two UL file lines from this block.

Flexibar sleeve rows in brochure P1349W-USEN, opened November 8, 2026.
NameSleeveWorking temperatureThicknessNominal voltageFinish
Flexibar AdvancedTPE, halogen-free, low smoke, flame retardant-50°C to 115°C1.8 mm (0.070 in)UL/CSA/IEC: 1,000 VAC and 1,500 VDCTinned
Flexibar StandardPVC, flame retardant-50°C to 105°C2 mm (0.078 in)UL/CSA/IEC: 1,000 VAC and 1,500 VDCTinned or plain
Flexibar SummumSilicone, halogen-free, flame retardant-50°C to 280°C2 mm (0.078 in)IEC: 1,000 VAC and 1,500 VDCPlain

Halogen-free and low smoke are Advanced lines, and Summum shares the halogen-free tests

The halogen-free section, as of November 8, 2026, says a halogen-free material does not contain fluorine, chlorine, bromine, iodine, or astatine, and it names chlorine as the element used for PVC. It says Flexibar Advanced and Flexibar Summum are halogen-free conductors, tested to IEC 60754-1, IEC 62821-2, and UL 2885. Standard is the PVC row, so the halogen-free sentence does not include it. The low-smoke rating row prints IEC 61034-2, UL 2885, and ISO 5659-2 for Advanced, and dashes for Standard and for Summum. The low-smoke section says Flexibar Advanced is a low smoke conductor. UV rating UL 2556 and UL 854 is printed on the Advanced column. The Standard and Summum UV cells in that row are dashes.

Railway fire classification is a separate pair. As of November 8, 2026, the brochure says Flexibar Summum conforms to EN 45545 with an HL3 classification for chapters R22 and R23. Flexibar Advanced conforms to EN 45545 with an HL2 classification for chapters R22 and R23. The same page says HL1 is the lowest hazard level and HL3 is the highest, and that the vehicle class depends on time in tunnels and whether the vehicle has sleeper cars. Standard is not given an HL line in those two sentences. A rail request that names HL3 copies Summum. A rail request that names HL2 copies Advanced.

Advanced and Standard may touch metal. Summum uses insulated spacers

The Class II section, opened November 8, 2026, says Flexibar Advanced and Flexibar Standard have Class II insulation certification according to IEC 61439-1, from dielectric strength greater than 20 kV/mm, mechanical resistance IK 09, and glow-wire resistance at 960°C. It says that certification allows touching and fixing directly to metal parts, with no clearance distance needed, and a maximum operating current up to 100% of the conductor maximum rated temperature. The same paragraph prints 105°C for Flexibar Standard and 115°C for Flexibar Advanced as that 100% temperature. It says a conductor that does not meet the requirement is subject to additional short-circuit test 10.11. The basic-insulation example on the same page is limited to 80% of the maximum permissible conductor operating temperature.

The fixing section says Flexibar Summum must not be fixed directly on a live part and needs insulated spacers. Advanced and Standard, because they are Class II, may touch conductive parts, and the brochure says fixing is not required when there are no sharp edges and no nearby electrical device. Where sharp edges are present, it recommends fixed spacers or ties secured to the framework every 400 mm, for any short-circuit level. A plastic tie, when that is the fastener, is a minimum width of 4.5 mm, tightened by hand. The last spacer or tie should be as close as possible to the device connection. Creepage between a metal part and a stripped Flexibar end is still a distance the standard requires. The brochure does not print that creepage number in millimeters.

Above 2,000 m, the brochure prints a derating for current and for voltage

The altitude section, as of November 8, 2026, says a conductor used above 2,000 m needs a reduction for dielectric strength and for cooling, and that the table is abstracted from DIN 43671 as a reference for rigid busbar and for Flexibar. Above 2,000 m the factor is 0.99 for ampacity and 0.99 for voltage. Above 3,000 m both factors are 0.96. Above 4,000 m the ampacity factor is 0.9 and the voltage factor is 0.8. Those factors multiply the current from the IEC or UL table and the nominal voltage on the sleeve row. The brochure also says IEC 61439 ambient air does not exceed +40°C, and that the average over 24 hours does not exceed +35°C. It recommends that the temperature rise for a normal Flexibar application does not exceed 50°C when the air inside the panel is below 40°C.

What to copy onto the Flexibar line

  • Name: Flexibar Advanced, Flexibar Standard, or Flexibar Summum, from brochure P1349W-USEN opened November 8, 2026.
  • Sleeve and temperature: TPE at -50°C to 115°C, PVC at -50°C to 105°C, or silicone at -50°C to 280°C.
  • Voltage: 1,000 VAC and 1,500 VDC, and whether the cell is UL/CSA/IEC or IEC only.
  • Thickness: 1.8 mm for Advanced, or 2 mm for Standard and Summum.
  • Finish: tinned, tinned or plain, or plain, from that row.
  • Mounting: Class II touch for Advanced and Standard, or insulated spacers for Summum. Ties every 400 mm when edges are sharp.
  • Altitude factor, when the site is above 2,000 m: 0.99, 0.96, or the 4,000 m pair of 0.9 and 0.8.
  • Section and rise current from the IEC or UL page, after the altitude factor if that factor applies.

Flexibar sleeve note

Name Advanced, Standard, or Summum. Copy the temperature and the mounting rule from that row.

This prepares a request. It does not send one.

Questions this brochure answers

Which sleeve is 115°C and halogen-free?

Flexibar Advanced is TPE at -50°C to 115°C, halogen-free, and low smoke, as of November 8, 2026. Standard is PVC at -50°C to 105°C. Summum is silicone at -50°C to 280°C and is halogen-free on the test list. Summum's low-smoke cells in the rating row are dashes.

Which Flexibar may be fixed against metal?

Advanced and Standard are the Class II rows, as of November 8, 2026, at 115°C and 105°C. Summum needs insulated spacers and must not be fixed directly on a live part.

Which name carries HL3?

Summum is the EN 45545 HL3 classification for chapters R22 and R23, as of November 8, 2026. Advanced is HL2 for the same two chapters.

Sources

Sleeve compound, temperature, thickness, voltage, finish, halogen-free tests, EN 45545 classes, Class II mounting, the 400 mm spacing, and the altitude factors are from nVent ERIFLEX brochure P1349W-USEN. It was opened November 8, 2026.