Industrial networking
Belden 2100A at 300 V or 2118A at 600 V
Use 2100A for the 300 V Type A extra-rugged row at 5.86 Ohm/1000ft. Use 2118A for the 600 V Type A TC-ER row at 7.06 Ohm/1000ft. Both list 0.319 in and 8.7 A.
On this page
Use Belden 2100A when the extra-rugged 18 AWG pair is the 300 V row. As of November 6, 2026, that sheet lists a TPE jacket of 0.319 in (8.10 mm), 8.7 A per conductor with no temperature in the cell, conductor DCR of 5.86 Ohm/1000ft (19.2 Ohm/km), and a voltage cell of 300 V. Use Belden 2118A when the row is 600 V. As of the same day, that sheet lists the same 0.319 in (8.10 mm), the same 8.7 A with no temperature in the cell, conductor DCR of 7.06 Ohm/1000ft, and a voltage cell of 600 V. The category places 2100A on 300 V Type A PLTC/ITC-ER, extra rugged, XLPE, and 2118A on 600 V Type A TC-ER, extra rugged, XLPE. The PVC industrial row at 5.2 A is on the 1334A and 2100A page.
The same 0.319 in TPE jacket, and a different shield stack
As of November 6, 2026, both titles say one pair, 18 AWG 7x26 tinned copper, XLPO insulation, and a TPE jacket. Both insulation cells say XLPE, cross-linked polyethylene, thermoset, colors blue, orange, and numbered. 2100A's inner shield is a 100% bi-laminate tape and a tinned-copper line with no coverage percent. The jacket cell does not print a thickness. 2118A's inner shield matches that tape and that tinned-copper line, and it adds an outer shield of bi-laminate with no coverage percent in that cell. The jacket cell prints thickness 0.047 in (1.2 mm) and the same nominal diameter 0.319 in (8.10 mm), with a ripcord. 2118A's title ends in 600V TC. The NEC line on that sheet is Article 336, TC-ER. Outer-shield DCR is printed on 2118A at 1.48 Ohm/1000ft (4.86 Ohm/km). 2100A's electrical block does not print an outer-shield DCR.
| Item | 2100A | 2118A |
|---|---|---|
| Category row | 300 V Type A, extra rugged | 600 V Type A TC-ER, extra rugged |
| Voltage cell | 300 V | 600 V |
| Jacket | TPE, 0.319 in, no thickness | TPE, 0.047 in, 0.319 in |
| Conductor DCR | 5.86 Ohm/1000ft | 7.06 Ohm/1000ft |
| Current | 8.7 A, no temperature | 8.7 A, no temperature |
| NEC line | CMG, ITC, PLTC | Article 336, TC-ER |
| Pull tension | 57 lbs | 44.8 lbs |
| Bend radius | No bend-radius cell in the text read | 3.19 in |
100 Ohm and 8.7 A match, and the DCR does not
As of November 6, 2026, both sheets list capacitance of 22 pF/ft (72 pF/m), unbalance of 1.2 pF/ft, impedance of 100 Ohm, inductance of 0.22 µH/ft (0.72 µH/m), and velocity of 64%. Current is 8.7 A per conductor on both, with no temperature in either cell. Insertion loss is 0.08 dB/100ft on both, with no frequency on that line. The conductor DCR split is 5.86 Ohm/1000ft (19.2 Ohm/km) on 2100A and 7.06 Ohm/1000ft on 2118A, and the 2118A cell does not print a kilometer figure. 2100A's NEC / UL line is Article 725, Article 727, Article 800, CMG, ITC, PLTC. 2118A's NEC / UL line is Article 336, TC-ER. Both AWM lines print AWM I A/B II A/B, C22.2 #230 Type TC, and C22.2 #239 Type CIC. CEC compliance on 2100A is CIC, TC. The 2118A standards block that was read does not print a CEC line.
90°C wet/dry on both, and burial is on the 2118A suitability cell
As of November 6, 2026, both UL cells print 90°C wet/dry. On 2100A the operating string aligned with the Operating header is -40°C to +90°C, and the installation cell is -25°C. The row also prints -25°C cold impact and -55°C cold bend. On 2118A the temperature headers that were read are UL Temperature and Operating. The row prints 90°C wet/dry, -25°C cold impact, -40°C to +90°C, and -55°C cold bend. It does not print a separate installation-temperature cell. Bend radius on 2118A is 3.19 in (81.0 mm), stationary and installation. 2100A does not print a bend-radius cell in the text that was read. Pull tension is 57 lbs (26 kg) on 2100A and 44.8 lbs (20.3 kg) on 2118A. Bulk weight is 51 lbs/1000ft on both. 2100A also prints 76 kg/km. 2118A's weight cell does not. Suitability on 2118A adds burial and prints oil resistance twice. Suitability on 2100A does not print burial. Flammability on 2118A is UL1581 vertical tray, 1202, and IEC 60332-3-24. Flammability on 2100A is UL1685 FT4 Loading and IEC 60332-3-24.
Light blue at 1,000 ft is a 2118A row
As of November 6, 2026, 2100A lists 2100A 0065000 light blue at 5,000 ft, 2100A 0031000 orange at 1,000 ft, and 2100A 0035000 orange at 5,000 ft. 2118A lists 2118A 0061000 light blue at 1,000 ft, 2118A 0065000 light blue at 5,000 ft, and 2118A 0035000 orange at 5,000 ft. Neither table prints footnote C. Page revision is 0.662, dated 10-30-2026, on 2100A, and 0.546, dated 09-07-2025, on 2118A. Neither sheet prints ISA/SP-50 Type A in the standards block that was read. The category page is the page that calls both extra rugged XLPE, one at 300 V Type A and one at 600 V Type A TC-ER.
What to copy onto the cable line
- Part: 2100A or 2118A, from the sheet opened November 6, 2026.
- Category row: 300 V Type A extra rugged, or 600 V Type A TC-ER extra rugged.
- Jacket: TPE at 0.319 in. 2118A also prints thickness 0.047 in.
- Insulation cell: XLPE thermoset. Both titles say XLPO.
- Impedance: 100 Ohm. Current: 8.7 A, with no temperature in the cell, on both.
- Conductor DCR: 5.86 Ohm/1000ft, or 7.06 Ohm/1000ft.
- Voltage cell: 300 V, or 600 V. NEC: CMG, ITC, PLTC, or Article 336, TC-ER.
- UL temperature: 90°C wet/dry on both. 2118A's title also says 600V TC.
Questions these pages answer
Does 600 V change 0.319 in?
Both nominal jacket diameters are 0.319 in (8.10 mm), as of November 6, 2026. 2118A also prints jacket thickness 0.047 in. 2100A's jacket cell does not print a thickness. Conductor DCR and the voltage cell are the split.
Does the 2118A title say TC-ER?
2118A's title says 600V TC, as of November 6, 2026. The NEC line says Article 336, TC-ER. The category row says 600 V Type A TC-ER. The request can carry each string with the line that printed it.
Which shield DCR is on 2100A?
2100A's electrical block that was read does not print an outer-shield DCR, as of November 6, 2026. 2118A prints 1.48 Ohm/1000ft (4.86 Ohm/km). Conductor DCR stays 5.86 Ohm/1000ft on 2100A and 7.06 Ohm/1000ft on 2118A.
Sources
Voltage, DCR, diameter, and the NEC line are from the Belden 2100A and 2118A technical data sheets. The 300 V and 600 V Type A labels are from the Belden Foundation Fieldbus category. All three were opened November 6, 2026. Neither sheet names the other part number.