Belden 3076F Flexible Foil or 1334A Braid for Type A

Use 3076F for the Type A flexible row, foil only, at 0.280 in and 5.2 A at 25°C. Use 1334A for the Type A industrial row, foil plus a 65% braid, at 0.287 in and 5.2 A.

Rust Belt Industrials · November 6, 2026 · 6 min read

On this page

Use Belden 3076F when the 18 AWG Foundation Fieldbus cable is the flexible foil row. As of November 6, 2026, that sheet lists a PVC jacket of 0.280 in (7.11 mm), 5.2 A per conductor at 25°C, conductor DCR of 7.2 Ohm/1000ft, and 100 Ohm. Use Belden 1334A when the same gauge is the industrial row with a 65% tinned-copper braid. As of the same day, that sheet lists a PVC jacket of 0.287 in (7.29 mm), 5.2 A per conductor with no temperature in that cell, the same 7.2 Ohm/1000ft, and the same 100 Ohm. The Foundation Fieldbus category places both numbers under 300 V Type A PLTC/ITC-ER, 18 AWG, one pair: 3076F on Flexible, and 1334A on Standard Industrial-grade. The 22 AWG Type B row is on the 3076F and 3077F page.

Foil and a 20 AWG drain, or foil plus a 65% braid

As of November 6, 2026, 3076F's title is Fieldbus, 1 pair 18 AWG stranded tinned copper, polypropylene insulation, overall shield, PVC jacket, flexible, sunlight resistant, oil resistant, PLTC-ER, ITC-ER, CMX-Outdoor, CM. The shield block is one 100% bi-laminate tape and a 20 AWG (7x28) tinned-copper drain. There is no braid line. Outer-shield DCR is 8.5 Ohm/1000ft (28 Ohm/km). 1334A's title is Fieldbus, 1 pair 18 AWG stranded tinned copper, PO insulation, overall shield plus tinned-copper braid, PVC jacket, CMG. The shield block is a 100% bi-laminate tape and a tinned-copper braid at 65%. The shield table does not print a drain gauge. Outer-shield DCR is 3.8 Ohm/1000ft (12 Ohm/km). The description says PO insulation. The insulation cell says polypropylene, colors blue and orange. 3076F's insulation cell is polypropylene, 0.022 in (0.56 mm) thick, nominal insulation diameter 0.088 in (2.2 mm), colors blue and orange. 1334A's insulation cell does not print a thickness.

3076F and 1334A rows from the sheets and the category page opened November 6, 2026.
Item3076F1334A
Category rowType A, flexibleType A, standard industrial-grade
ShieldFoil, 20 AWG drainFoil plus 65% tinned-copper braid
JacketPVC, 0.280 inPVC, 0.287 in
Current5.2 A at 25°C5.2 A, no temperature in the cell
Shield DCR8.5 Ohm/1000ft3.8 Ohm/1000ft
Voltage cell300 V (CM, PLTC-ER)300 V RMS
UL temperature105°C90°C
Operating range-40°C to +105°C-40°C to +105°C

100 Ohm and 7.2 Ohm/1000ft, with a different shield DCR

As of November 6, 2026, both conductor-DCR cells print 7.2 Ohm/1000ft and do not print a kilometer figure. Both list capacitance conductor to shield of 45 pF/ft (150 pF/m), maximum capacitance unbalance of 1.2 pF/ft, characteristic impedance of 100 Ohm, and velocity of 66%. 3076F lists inductance of 0.19 µH/ft (0.62 µH/m). 1334A's electrical block that was read does not print an inductance cell. 3076F's current cell is 5.2 A per conductor at 25°C. 1334A's current cell is 5.2 A per conductor and does not print a temperature. Insertion loss on 3076F is 0.08 dB/100ft at 0.039 MHz. Insertion loss on 1334A is 0.069 dB/100ft, and that line does not print a frequency. Voltage on 3076F is 300 V (CM, PLTC-ER) and 150 V (ITC-ER). Voltage on 1334A is 300 V RMS. NEC / UL compliance on 3076F is Article 725, Article 727, Article 800, CMG, ITC, PLTC, TC. On 1334A it is Article 725, Article 727, Article 800, CMG, ITC, PLTC. CEC compliance is CMG on both.

0.280 in at UL 105°C, or 0.287 in at UL 90°C

As of November 6, 2026, 3076F's jacket is PVC, 0.050 in (1.3 mm) thick, nominal diameter 0.280 in (7.11 mm), with a jacket OD note of plus or minus 0.010. UL temperature is 105°C. Operating temperature is -40°C to +105°C. Stationary bend radius is 6.5 in (170 mm). Installation bend radius is 2.80 in (71.1 mm). Pull tension is 60 lbs (27 kg). Bulk weight is 44 lbs/1000ft. 1334A's jacket is PVC, 0.065 in (1.7 mm) thick, nominal diameter 0.287 in (7.29 mm), with a ripcord. UL temperature is 90°C. Operating temperature is -40°C to +105°C. Those two 1334A cells do not share a high end. Stationary and installation bend radius are both 3.37 in (85.6 mm). Pull tension is 44.8 lbs (20.3 kg). Bulk weight is 60 lbs/1000ft, with no kilogram in that cell. Suitability on 3076F lists indoor, outdoor, sunlight resistance, oil resistance twice, and burial. Suitability on 1334A lists indoor, outdoor, sunlight resistance, UV resistance, and oil resistance twice. It does not print burial.

ISA/SP-50 Type A is on the 3076F sheet

As of November 6, 2026, 3076F lists ISO/IEC compliance IEC 61158-2 and other-standard compliance ISA/SP-50 Type A. Flammability is UL 1685 UL Loading, FT4, IEEE 1202, and IEC 60332-1-2. CPR is Euroclass Eca and UKCA Class Eca. 1334A's standards block that was read does not print IEC 61158-2 or ISA/SP-50 Type A. Flammability is UL1685 FT4 Loading, 1202, and IEC 60332-3-24. CPR is Euroclass Eca. The category page is the page that calls 1334A Type A. Page revision is 0.536, dated 02-20-2026, on 3076F, and 0.569, dated 02-20-2026, on 1334A. The category footnote says CPE jacketed versions for increased chemical resistance are available upon request. It does not name a CPE part number for either cable.

Light blue rows on both, and a 3,280 ft row only on 1334A

As of November 6, 2026, 3076F's notes say an orange jacket is Fieldbus and an intrinsically safe blue jacket is PROFIBUS PA. The light blue row is 3076F 0061000 at 1,000 ft, footnote C. Orange rows that print a length include 3076F 0031000 at 1,000 ft and 3076F 0035000 at 5,000 ft. 1334A lists 1334A 0061000 light blue at 1,000 ft, 1334A 0063280 light blue at 3,280 ft, 1334A 0031000 orange at 1,000 ft, and 1334A 0033280 orange at 3,280 ft, each with footnote C, crate reel put-up. 1334A does not print the orange-versus-blue sentence. The XLPE jacket at 8.7 A is on the 1334A and 2100A page. The two-pair industrial PVC cable is on the 1334A and 1327A page.

What to copy onto the cable line

  • Part: 3076F or 1334A, from the sheet opened November 6, 2026.
  • Category row: 300 V Type A, flexible, or 300 V Type A, standard industrial-grade.
  • Conductor: 18 AWG 7x26 tinned copper. Impedance: 100 Ohm. Conductor DCR: 7.2 Ohm/1000ft.
  • Shield: foil and a 20 AWG drain, or foil plus a 65% tinned-copper braid.
  • Jacket: PVC at 0.280 in, or PVC at 0.287 in.
  • Current: 5.2 A at 25°C, or 5.2 A with no temperature in the cell.
  • Voltage cell: 300 V (CM, PLTC-ER) and 150 V (ITC-ER), or 300 V RMS.
  • Temperature: UL 105°C, or UL 90°C. Operating high is +105°C on both sheets.

3076F or 1334A note

Name the Type A row. Foil only is 3076F. Foil plus a 65% braid is 1334A.

This prepares a request. It does not send one.

Questions these pages answer

Does the braid change 5.2 A?

Both current cells print 5.2 A per conductor, as of November 6, 2026. Only 3076F prints 25°C in that cell. The braid changes the shield DCR, from 8.5 Ohm/1000ft to 3.8 Ohm/1000ft, and the jacket diameter, from 0.280 in to 0.287 in.

Does the 1334A sheet print Type A?

1334A's standards block that was read does not print ISA/SP-50 Type A, as of November 6, 2026. The category page is the page that places 1334A on the Type A standard industrial-grade row. 3076F's sheet does print ISA/SP-50 Type A.

Which high temperature is on 1334A?

1334A's UL temperature is 90°C, as of November 6, 2026. The operating range on that sheet is -40°C to +105°C. The request can carry both cells.

Sources

Shield, diameter, current, DCR, and temperature are from the Belden 3076F and 1334A technical data sheets. The Type A row labels are from the Belden Foundation Fieldbus category. All three were opened November 6, 2026. Neither sheet names the other part number.