Skip to the guide

Industrial networking

Beckhoff ZB9013 vs LAPP 2170891 for a Fixed Ethernet Run

Use ZB9013 for Beckhoff's yellow fixed Cat.5 cable at 6.5 mm ± 0.2 mm. Use 2170891 for PROFINET Type A at 6.3 mm and nom. 100 Ω.

Rust Belt Industrials · October 23, 2026 · Updated October 27, 2026 · 6 min read

On this page

Use Beckhoff ZB9013 when the line item is that fixed-installation cable: PVC jacket, yellow, Cat.5, outer diameter 6.5 mm ± 0.2 mm, as of the product page opened October 23, 2026. Use LAPP article 2170891 when the line item is PROFINET Type A: 2 x 2 x AWG22/1, outer diameter 6.3 mm, green sheath, nominal impedance 100 Ω according to IEC 61156-5. Beckhoff's wiring page limits the copper link between two EtherCAT devices to 100 m and asks for at least category 5 according to EN 50173 or ISO/IEC 11801. The LAPP Type A page says the same family is suitable for EtherCAT and EtherNet/IP, so 2170891 can be the cable when that sentence is the allowance and the green 6.3 mm article is the one named.

What the ZB9013 page prints

The technical-data table for ZB9013 lists cross-section 1 x 4 x 0.34 mm² (AWG22), use as fixed installation, jacket material PVC, outer diameter 6.5 mm ± 0.2 mm (0.2559 in ± 0.0079 in), minimum bending radius moved of 7.5 times the outer diameter, minimum bending radius fixed of 3 times the outer diameter, and jacket color yellow. The page sells it by the meter. The product title also reads 2 x 2 x AWG22, and a line under the photograph reads 1 x 4 x AWG22. The technical-data cell and the title do not use the same pair string. The request copies the technical-data cell, 1 x 4 x 0.34 mm² (AWG22), and notes the title string so the supplier can confirm which construction string to print. Outer diameter, color, Cat.5, and the two bend multipliers do not depend on that string.

The moved bend is 7.5 times the outer diameter. The fixed bend is 3 times the outer diameter. The page prints those multipliers, and the diameter they multiply is 6.5 mm ± 0.2 mm. The product page does not print a temperature range or an impedance. Those fields stay blank for ZB9013 until a sheet that prints them is attached to the request.

The wiring page sets the link length and the category

The EtherCAT wiring page says the cable length between two EtherCAT devices must not exceed 100 m. Cables should meet at least category 5 (Cat5) according to EN 50173 or ISO/IEC 11801. EtherCAT uses 4 wires for signal transfer and RJ45 connectors. The pin assignment is compatible with ISO/IEC 8802-3: pin 1 yellow TD+, pin 2 orange TD-, pin 3 white RD+, pin 6 blue RD-. Those pairs are the same colors PI uses for 4-core PROFINET, which is why the pair-color page cites both. Auto-crossing on Beckhoff EtherCAT devices allows a 1:1 cable or a cross-over cable.

The same wiring page lists cables it calls suitable for EtherCAT systems, including ZB9010 for fixed installation, CAT 5e, 4-core, and ZB9020 for drag chain, CAT 5e, 4-core. ZB9013 is not in that list. ZB9013 is a separate product page for a fixed Cat.5 cable. The 100 m limit and the Cat5 minimum are the wiring rules. They apply to the link. They are not a statement that ZB9013 is absent from Beckhoff's catalog. Diameters for ZB9010 and ZB9020 are on the ZB9010 and ZB9020 page. This page does not assign those cables the 6.5 mm yellow figures from ZB9013.

2170891 is the green 6.3 mm Type A article

LAPP article 2170891 is ETHERLINE PN Cat.5e Y, 2 x 2 x AWG22/1, core diameter 1.5 mm, outer diameter 6.3 mm. The family impedance is nom. 100 Ω according to IEC 61156-5. Peak operating voltage is 125 V, not for power applications. The sheath is PVC, green, based on RAL 6018, with a star quad and an overall copper braid plus foil screen. The page is Type A for fixed installation and states 10/100 Mbit/s for the 2-pair construction. It also says the cable is suitable for EtherCAT and EtherNet/IP. Temperature and bend radius on this catalog page say see data sheet, so they are not filled in from ZB9013's multipliers.

ZB9013 and LAPP 2170891 from the pages opened October 23, 2026. ZB9013 impedance and temperature were not on the product page.
ItemBeckhoff ZB9013LAPP 2170891
UseFixed installation, Cat.5PROFINET Type A, fixed installation, Cat.5
JacketPVC, yellowPVC, green, RAL 6018
Outer diameter6.5 mm ± 0.2 mm6.3 mm
Construction cell to copyTechnical data: 1 x 4 x 0.34 mm² (AWG22). Title also says 2 x 2 x AWG22.2 x 2 x AWG22/1, star quad
ImpedanceNot printed on the product pagenom. 100 Ω acc. to IEC 61156-5
Bend7.5 x OD moved, 3 x OD fixedSee data sheet on the catalog page

Which line item matches the port

A Beckhoff bill of material that names ZB9013 uses the yellow PVC cable at 6.5 mm ± 0.2 mm, fixed installation, with the wiring page's 100 m maximum between EtherCAT devices and at least Cat5. A PROFINET fixed run that names Type A uses 2170891 at 6.3 mm and nom. 100 Ω, or another article on that LAPP page if the diameter is 6.5 mm or 7.7 mm. When the allowance being used is LAPP's EtherCAT sentence, 2170891 is still the green article with a printed impedance, and ZB9013 is still the yellow article with a printed bend multiplier and no impedance on the product page.

Both pages describe fixed Cat.5 cable with four conductors in the construction strings, and the diameters differ by a few tenths of a millimeter before ZB9013's ± 0.2 mm tolerance. Color, the printed impedance, and the bend multipliers are the fields that keep the line items apart. PROFIBUS DP at 150 Ohm is a third cable, Belden 3079A, on the DP comparison.

What to copy onto the cable line

  • Product: ZB9013 or LAPP 2170891.
  • Jacket color: yellow or green.
  • Outer diameter: 6.5 mm ± 0.2 mm, or 6.3 mm.
  • Category and length: at least Cat5, and 100 m maximum between EtherCAT devices when the Beckhoff wiring page is the rule.
  • Construction string: the ZB9013 technical-data cell, with the title's 2 x 2 x AWG22 noted for confirmation, or 2 x 2 x AWG22/1 for 2170891.
  • Impedance: nom. 100 Ω for 2170891. Leave it blank for ZB9013 unless a sheet that prints it is attached.

Fixed Ethernet cable note

Name ZB9013 or the LAPP article, and the diameter on that page.

This prepares a request. It does not send one.

Questions these pages answer

Is 6.5 mm ± 0.2 mm the same article as 6.3 mm?

ZB9013 prints 6.5 mm ± 0.2 mm and a yellow jacket. 2170891 prints 6.3 mm and a green jacket. The article numbers and the colors are different line items.

Which ZB9013 construction string is the one to order?

The technical-data table prints 1 x 4 x 0.34 mm² (AWG22). The title prints 2 x 2 x AWG22. Both strings were on the page opened October 23, 2026. Copy the table cell onto the request and ask Beckhoff to confirm the title. Diameter, color, and bend radius do not wait on that confirmation.

Does the 100 m limit apply only to ZB9010?

The wiring page states the 100 m maximum between two EtherCAT devices before it lists example cables. ZB9010 and ZB9020 are examples on that list. The limit is the link length. ZB9013's product page does not print a different maximum.

Sources

ZB9013 diameter, color, bend multipliers, Cat.5 fixed use, and the two construction strings are from the Beckhoff product page. The 100 m limit, the Cat5 minimum, the 4-wire sentence, the pin colors, and the ZB9010 and ZB9020 names are from the EtherCAT wiring page. Article 2170891's diameter, impedance, sheath, pair count, and EtherCAT sentence are from the LAPP Type A catalog page. All three were opened October 23, 2026.