Skip to the guide

Industrial networking

Siemens 6XV1840-2AH10 Type A or 6XV1840-4AH10 Type B Marine

Use 6XV1840-2AH10 for Type A rigid PVC and 100 m at 100BaseTX. Use 6XV1840-4AH10 for Type B marine FRNC, halogen-free construction, and 85 m at 100BaseTX.

Rust Belt Industrials · October 28, 2026 · 7 min read

On this page

Use Siemens 6XV1840-2AH10 when the PROFINET cable is Type A with rigid cores for fast installation. As of October 28, 2026, that page lists a PVC sheath of 6.5 mm, impedance of 100 Ohm with a 15% relative symmetrical tolerance, and 100 m for 100BaseTX. Use Siemens 6XV1840-4AH10 when the cable is Type B for marine and offshore use. As of the same day, that page lists an FRNC sheath of 6.5 mm, impedance of 100 Ohm with a 5% relative symmetrical tolerance, a halogen-free construction, and 85 m for 100BaseTX. Both are IE FC TP 2x2 cables, 4-core, shielded, Cat5e, sold by the meter, with a minimum order quantity of 20 m. Type C trailing cable 6XV1840-3AH10 is a different article, on the 2AH10 and 3AH10 page.

Type A is the rigid installation article, Type B here is the marine article

The 2AH10 product type, as of October 28, 2026, is IE FC TP Standard Cable GP 2x2 (Type A). Suitability is a standard cable with rigid cores for fast installation. The description says it is a TP installation cable for connection to IE FC RJ45 2x2, for universal use, 4-core, shielded CAT 5E. Maximum delivery unit is 4,000 m. The mall page prints last modified 3/10/2026 and Date 10/15/2026. The 4AH10 product type is IE FC TP Marine Cable 2x2 (Type B). Suitability is marine and offshore use. The description says it is a halogen-free bus cable according to IEC 60754-1/2, for connection to an FC outlet RJ45, shipbuilding certified, 4-core, shielded, Cat5e. Maximum delivery unit is 1,000 m. That page prints last modified 3/10/2026 and Date 10/28/2026. Both brand lines say SIMATIC NET. Both say FastConnect yes. LAPP's Type B article is a different catalog page, on the PROFINET type page. This page uses the Siemens type letters on these two mall pages.

Same 6.5 mm sheath, PVC or FRNC, and a different inner conductor

As of October 28, 2026, both pages list 4 electrical cores, a shield described as SF/UTP, overlapped aluminum-clad foil, sheathed in a protective braided shield of tinned copper wires, insulation color white/yellow/blue/orange, and a green cable sheath. Sheath outer diameter is 6.5 mm on both, with a symmetrical tolerance of 0.2 mm. Wire insulation diameter is 1.5 mm on both. Inner sheath diameter is 3.9 mm on both. 2AH10's wire insulation is polyethylene, the inner sheath is PVC, and the cable sheath is PVC. The inner conductor diameter is 0.64 mm, and the AWG22 insulated-conductor cell is 0.64 mm. The cable designation is SF/UTP, 2YY (ST) CY 2x2x0,64/1,5-100 GN. 4AH10's wire insulation is PP, and the inner sheath and the cable sheath are both FRNC. The inner conductor diameter is 0.75 mm, and the AWG22 insulated-conductor cell is 0.75 mm. The cable designation is SF/UTP, L-9YH (ST) CH 2x2x0,34/1,5-100 GN VZN FRNC. That designation prints 0,34. The diameter cells on the same page print 0.75 mm. Copy the designation string and the diameter cell as separate lines.

6XV1840-2AH10 and 6XV1840-4AH10 rows from the mall pages opened October 28, 2026.
Item6XV1840-2AH106XV1840-4AH10
Type on the pageType A, rigid coresType B, marine and offshore
SheathPVC, 6.5 mmFRNC, 6.5 mm
Inner conductor0.64 mm0.75 mm
Impedance tolerance15%5%
100BaseTX length100 m85 m
Loop resistance maximum115 mΩ/m120 mΩ/m
Halogen-freeNoYes
600 V styleAWM 21694, 60°CNo

100 Ohm on both, with a different tolerance and a different link length

As of October 28, 2026, both pages list impedance of 100 Ohm from 1 MHz to 100 MHz. The relative symmetrical tolerance is 15% on 2AH10 and 5% on 4AH10. Attenuation maximum is 0.052 dB/m at 10 MHz and 0.195 dB/m at 100 MHz on 2AH10. It is 0.06 dB/m at 10 MHz and 0.22 dB/m at 100 MHz on 4AH10. Near-end crosstalk per length is 0.5 dB/m from 1 MHz to 100 MHz on both. Transfer impedance per length at 10 MHz is 10 mΩ/m on both. Loop resistance maximum is 115 mΩ/m on 2AH10 and 120 mΩ/m on 4AH10. Operating voltage RMS is 80 V on both. NVP is 69% on both. Test voltage is 2000 V AC core to core and 2000 V AC core to shield on both. The note on both pages says electrical properties are measured at 20°C. 100BaseTX length is 100 m on 2AH10 and 85 m on 4AH10.

Shipbuilding societies are on the Type B page

As of October 28, 2026, the marine classification block on 2AH10 prints No for ABS, BV, DNV, GL, LRS, NK, and PRS. The same block on 4AH10 prints Yes for ABS, BV, DNV, LRS, PRS, and RINA, and No for GL and NK. 4AH10's product description says the cable is shipbuilding certified. 2AH10's description does not. Halogen-free is No on 2AH10 and Yes on 4AH10. The 300 V listing on 2AH10 reads Yes; c(ETL)us / CMG / (ETL)us PLTC/ ITC / Sun Res. The 600 V style line reads Yes; cRUus AWM 21694 AWM I A/B 60°C 600V FT2. The 300 V listing on 4AH10 reads Yes; cULus / CMG / PLTC / Sun Res. The 600 V style line reads No. Both pages say Cat5e, EAC, CE, RoHS, and ANSI/ISA-71.04 G3. PoE and PoE+ are Yes on both. Silicon-free is Yes on both. The industrial-communication block on 4AH10 prints PROFIBUS Yes and PROFINET Yes.

The operation cell and the permanent-installation line on 4AH10

Operating temperature on 2AH10 is -40°C to +75°C, as of October 28, 2026. Storage, transport, and the same -40°C to +75°C span share that page. Installation is -40°C to +60°C. Operating temperature on 4AH10, in the during-operation cell, is -25°C to +70°C. Storage and transport are -40°C to +85°C. Installation is 0°C to +50°C. A separate ambient-condition line on 4AH10 says the temperature range for permanent installation is -40°C to 85°C. That line is not the during-operation cell. Copy the labeled cell the drawing asks for. 4AH10 does not print a continuous-bending cell or a bending-cycle count. Single-bend minimum is 19.5 mm on 2AH10 and 39 mm on 4AH10. Multiple-bend minimum is 49 mm on 2AH10 and 97.5 mm on 4AH10. Tensile load maximum is 150 N on both. Weight is 61 kg/km on 2AH10 and 68 kg/km on 4AH10.

Fire behavior on 2AH10, as of October 28, 2026, is flame resistant according to IEC 60332-3-24 (Category C) and UL 1685 (CSA FT 4). Fire behavior on 4AH10 is flame resistant according to IEC 60332-3-22 (Category A/F), and smoke density according to IEC 61034-1/2. Burning class according to EN 13501-6 is Eca on both. Oil resistance on 2AH10 is oil resistant according to IEC 60811-2-1 (4 h / 70°C). Oil resistance on 4AH10 is conditional resistance, IEC 60811-2-1 (4 hours / 70°C). Grease and water are conditional resistance on both. UV radiation is resistant on both.

What to copy onto the cable line

  • Article: 6XV1840-2AH10 or 6XV1840-4AH10, from the mall page opened October 28, 2026.
  • Type: Type A rigid cores, or Type B marine and offshore, including halogen-free and the society lines if the article is 4AH10.
  • Sheath: PVC or FRNC, 6.5 mm, symmetrical tolerance 0.2 mm, and the inner-conductor diameter 0.64 mm or 0.75 mm.
  • Designation: 2x2x0,64 on 2AH10. On 4AH10, the designation string 2x2x0,34 and the 0.75 mm diameter cell, as separate lines.
  • Impedance: 100 Ohm, with 15% or 5% relative symmetrical tolerance.
  • 100BaseTX: 100 m, or 85 m.
  • Listing: CMG / PLTC / ITC / Sun Res and AWM 21694, or CMG / PLTC / Sun Res and 600 V marked No.
  • Order length: sold by the meter, minimum order quantity 20 m, maximum delivery unit 4,000 m or 1,000 m.

6XV1840-2AH10 or 6XV1840-4AH10 note

Name Type A or Type B marine, and copy the 100BaseTX length from that page.

This prepares a request. It does not send one.

Questions these pages answer

Does Type B on 4AH10 mean the trailing cable?

4AH10's product type says Type B, and its suitability line says marine and offshore use, as of October 28, 2026. It does not print a bending-cycle count. The trailing-cable article with 4 million cycles is 6XV1840-3AH10.

2AH10 prints 100 m for 100BaseTX, as of October 28, 2026. 4AH10 prints 85 m. Both impedance cells are 100 Ohm. The tolerance is 15% on 2AH10 and 5% on 4AH10.

Which temperature line is the operating range on 4AH10?

The during-operation cell is -25°C to +70°C, as of October 28, 2026. The ambient-condition line says permanent installation from -40°C to 85°C. The two lines stay separate on the request.

Sources

Type, sheath, impedance tolerance, 100BaseTX length, marine classification, temperature, and the order-quantity lines are from the Siemens mall data pages for 6XV1840-2AH10 and 6XV1840-4AH10. Both were opened October 28, 2026. The 2AH10 page date line is 10/15/2026. The 4AH10 page date line is 10/28/2026.